COMPRESSOR SENSOR SYSTEM ABNORMAL
Possible Root
1. Broken and disconnected harness.
cause
2. Outdoor unit PCB defective.
3. Defective compressor.
Troubleshooting
H0 (Class 18/24)
Check reactor connection.
Any abnormal?
No
Check reactor resistance.
Yes
Check compressor resistance.
Yes
Change outdoor PCB.
Yes
# Disconnect the reactor wire and measure
resistance between terminal.
No
No
Service Diagnosis
Connect back reactor.
Change reactor.
Change Compressor.