  • Page 1: And Maintenance

    120 Series Loudspeaker, ISMT Loudspeaker, Powered Loudspeaker, and Sounder 25 Watts (Model Type ES4 and ES5) Installation, Operation, and Maintenance 2562192D REV. D 612 Printed in U.S.A.
  • Page 2 8 hereof must be fully explained in writing and received by Seller within thirty days after Buyer learns of the defect or such claim shall be deemed waived. Federal Signal Corporation Integrated Systems 2645 Federal Signal Drive...
  • Page 3: Table Of Contents

    Contents Safety Message to Installers, Operators, and Maintenance Personnel ...............5 An Overview of the 120 Series ............6 Product Detail ..................7 Special Conditions for Safe Use .............9 Condições especiais para o Uso Seguro: ...........10 Installing the Product .................11 Accessing the Terminals and Glands ........... 11 Earthing ....................12...
  • Page 4 120 Series Loudspeakers and Sounder Tables Table 1 Tone chart for 240 Vac, 110 Vac, and 24 Vdc two-wire operation ............16 Table 2 Tone chart for 24 Vdc 3-to-5 wire and AC 4-to-6 wire operation ............... 18 Table 3 Replacement parts ..............19...
  • Page 5: Safety Message To Installers, Operators, And Maintenance Personnel

    120 Series Loudspeakers and Sounder Safety Message to Installers, Operators, and Maintenance Personnel It is important to follow all instructions shipped with this product. This device is to be installed by a trained electrician who is thoroughly familiar with local codes.
  • Page 6: An Overview Of The 120 Series

    120 Series Loudspeakers and Sounder An Overview of the 120 Series The Federal Signal 120 Series Loudspeaker complies with the ATEX Directive for operation in gaseous hazardous areas classified as Zone 1 with a temperature classification of –20 °C to +70 °C T4, –20 °C to +55 °C T5, and –20 °C to +40 °C T6.
  • Page 7: Product Detail

    120 Series Loudspeakers and Sounder Product Detail Frequency Range: Explosion Proof Marine 350–4000 Hz 300–3700 Hz Ambient Temperature Range: T4 Explosion Proof T5 Explosion T6 Explosion and Marine Proof Proof –20 °C to +70 °C –20 °C to +55 °C –20 °C to +40 °C...
  • Page 8: Specifications

    100 volt, 70 volt, and 8 ohms Power Capacity 25 W FIRE/EXPLOSION HAZARD Do not use the 120 Series in flammable atmospheres contain- ing carbon disulphide (CS ). All units are not certified for use in flammable atmospheres containing carbon disulphide. Failure to observe this warning could result in serious injury or death.
  • Page 9: Special Conditions For Safe Use

    120 Series Loudspeakers and Sounder SHOCK HAZARD Do not connect this unit to the system while the power is on. Failure to heed this warning could cause serious injury or death. Figure 1 Loudspeaker dimensions 229 mm 315 mm (9.02 in) (12.4 in)
  • Page 10 120 Series Loudspeakers and Sounder Check label details to ensure the unit is of the correct electrical rat- ing and hazardous area classification. For permanently connected equipment located in safe areas, the equipment supply should be provided via a disconnect device lo-...
  • Page 11: Installing The Product

    120 Series Loudspeakers and Sounder Installing the Product This product must be installed and maintained only by qualified per- sonnel who have received the relevant training. During installation ensure that all external screw threads and flameproof faces are suit- ably greased. Recommended torque on all external fixings is 5 N • m.
  • Page 12: Earthing

    120 Series Loudspeakers and Sounder Figure 3 Side and rear views REAR VIEW SIDE VIEW M5 CAP SCREW (4) RACHETED BRACKET (2) M20 GLAND 290A6313 ENTRIES (2) Figure 4 Tapping TRANSFORMER TAPPINGS TERMINALS NOTE: ENSURE THE SOUNDER IS 1 AND 2 25 W 2.0 W...
  • Page 13: Greasing Holes For The Mounting Face And Screws

    120 Series Loudspeakers and Sounder Figure 5 Speaker wiring diagram VOLUME CONTROL: TURN CLOCKWISE TO INCREASE VOLUME INTERNAL EARTH IN LID 1 2 3 4 5 6 7 8 9 10 REAR VIEW EXTERNAL 2 x M20 GLAND EARTH ENTRIES...
  • Page 14: Wiring The Es4/Ms4 Multi-Tone Sounder

    120 Series Loudspeakers and Sounder Wiring the ES4/MS4 Multi-Tone Sounder This section provides instructions for operating the Multi-Tone Sound- er at 240 Vac, 110 Vac, and 24 Vdc. Also included are instructions for 24 Vdc 2-wire operation, 24 Vdc 3-to-5-wire operation, and AC 4-to-6-wire operation. See Figures 6 and 7 on page 15 and the Table 1 on page 16.
  • Page 15: Figure 6 Sounder Wiring Diagram

    120 Series Loudspeakers and Sounder Figure 6 Sounder wiring diagram TONE SELECTOR DETAIL OF 12-CONNECTOR TERMINAL BLOCK REAR VIEW INTERNAL EARTH IN LID EXTERNAL 2 x M20 GLAND 290A6315 EARTH ENTRIES Figure 7 Voltage selector for multi-tone sounder VOLTAGE SELECTOR...
  • Page 16: For 24 Vdc 3-To-5-Wire Operation

    120 Series Loudspeakers and Sounder Table 1 Tone chart for 240 Vac, 110 Vac, and 24 Vdc two-wire operation Position Tone Two tones: 588 Hz for 0.25 second, 714 Hz for 0.25 second Swept 600 Hz > 700 Hz in 0.5 second...
  • Page 17: For Ac 4-To-6-Wire Operation

    120 Series Loudspeakers and Sounder For AC 4-to-6-Wire Operation See Figures 6 and 7 on page 15 and the tone chart on page 18. 240 Vac Operation: 1. Set the Voltage Selector to 230 V. 2. Insert the 250 mA fuse, 3.
  • Page 18: Routine Maintenance

    120 Series Loudspeakers and Sounder Table 2 Tone chart for 24 Vdc 3-to-5 wire and AC 4-to-6 wire operation Terminal Tone Two tones: 588 Hz for 0.25 second, 714 Hz for 0.25 second Swept 600 Hz > 700 Hz in 0.5 second Constant 700 Hz 700 Hz for 0.25 second, silence for 0.25 second...
  • Page 19: Technical Service And Support

    120 Series Loudspeakers and Sounder Technical Service and Support For technical service and support, please contact: Federal Signal Corporation Integrated Systems Service Department 2645 Federal Signal Drive University Park, IL 60484-3167, U.S.A. Phone: +1 877 289 3246 Fax: +1 708 534 4887 E-Mail: systems@fedsig.com...