Download Print this page

Siemens VersiCharge Quick Start Manual page 2

Electric vehicle charging station

Advertisement

DANGER Hazardous Voltage
Wire Outlet (continued)
2
(Skip this step if hardwiring the unit)
Will cause death, serious injury or
substantial property damage.
Turn off power supplying
equipment before working inside.
Run Wire (If a 240V receptacle is already
installed in the desired installation location
1
with a dedicated 40 A circuit, please skip to
step 3)
A dedicated 40 amp, 2 pole
circuit breaker is required.
Ensure there is empty space
Snake wiring through wall or run conduit on exposed
in the load center and that
surfaces.
the electrical system has
sufficient capacity for a
Select location and add mounting bracket
continuous 30 A load.
3
(match bracket location with orientation of
the ground hole as shown below)
Wire conductors (copper only) per
all NEC and local jurisdiction
requirement. Snake wiring through
walls or run conduit on exposed
surfaces. Be sure to tighten down
wire in circuit breakers per
manufacturer's recommendation.
NOTE: Please consider your planned installation location for
the mounting bracket when choosing the location to which
you will run the wire.
Wire Outlet
2
(Skip this step if hardwiring the unit)
WARNING! When
installed outdoors, due
to the risk of moisture,
cord and plug installations
require a NEMA outdoor
rated receptacle and
enclosure. Installing
outdoors without properly
rated outdoor receptacles
and enclosures will violate
listings and void the device warranty. Outdoor cord-and- plug
installations must be bottom fed only.
DANGER Explosion Hazard
This equipment has arcing or
sparking parts that should not be
Locate a stud within the wall that can handle the 14+ lb load of
exposed to flammable vapors. This
the VersiCharge. For concrete or other walls, install appropriate
equipment should be installed
anchors. If using receptacle, ensure that power cord will reach to
at least 18 inches above floor or
the outlet.
ground level. Use extreme caution
Using a 7/16" socket, attach mounting bracket to wall in
and follow instructions carefully.
compliance with all National Electrical Code® (NEC) and local
jurisdiction requirements, using the 2 lag screws provided.
VersiCharge Quick Start Guide
DANGER Hazardous Voltage
6
Screw down charging station
Will cause death, serious injury or
substantial property damage.
Turn off power supplying
equipment before working inside.
3.b Wire up VersiCharge
4
(Skip if using receptacle)
7
Check System
5
Mount VersiCharge
Turn power on and the green Power Available light should
illuminate. If it does not, verify that the outlet or wire is
putting out 240 or 208 VAC.
With the Power Available light on, plug the EVSE into the car.
If you have any fault lights, please consult Installation and
Operations Manual on the provided USB key chain.
WARNING! Do not force the connector into the receiver
on the vehicle. If the connection between the receiver and
connector shows any resistance, inspect the pins in each, and
if damage is found, call a qualified service person.
2
1
4
3
5
1.
Pause/Reset Button
2.
Charging
3.
Fault*
4.
Power Available
5.
Infrared Service Portal
6.
Time Delay Button (2/4/6/8 hr delay options)
* For troubleshooting information refer to the complete Installation and Operations manual on the USB key chain provided or call technical support
1-800-241-4453.
Technical support: 1-800-241-4453
Visit our website: www.usa.siemens.com/versicharge
6
VersiCharge Quick Start Guide

Advertisement

loading