Vacon NX Series Applications Manual page 138

Marine application (apfiff09)
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

138 • Vacon
P2.6.2.12 Scaling of Generating power limit
The generator power limit is equal to parameter Generator Power Limit if value 'Not
Used' is selected. If any of the inputs is selected the generator power limit is scaled
between zero and parameter P2.6.2.2 Generator Power Lim.
0 = Parameter
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FieldBus Scaling ID46 (Monitoring Value)
P2.6.2.13 Undervoltage power limit DC level
This parameter defines the DC voltage level when the special power limit function is
activated. When DC voltage goes below this level the power level defined by under
voltage power limit will be activated.
P2.6.2.14 Undervoltage power limit
Defines the power limit that is used when DC voltage is below parameter Undervoltage
power limit DC level (P2.6.2.13). The function is deactivated when this parameter value is
zero.
6
ID1612
DC Level
UV Level
Power Limit
UV P Lim
ID1088
ID1611
Tel. +358
apfiff09 marine