Technical data
Mechanical testing
Vibrations (DIN class B)
Measuring accuracy
The accuracy is defined as the higher value of general values and basic values.
General values
Input type
All
Basic values
Input type
Pt100 and Pt1000
Ni100
Cu10
Resistance-type transmitter
Voltage sensor
Thermocouple type:
E, J, K, L, N, T, U
Thermocouple type:
B, R, S, W3, W5
Cold junction compensation
Reference conditions
EMC
Regulations observed
EMC 2004/108/EC Emission and interference
immunity
EMC of interference voltage influence
Extended EMC interference immunity:
NAMUR NE 21, criterion A, burst
40
Heat-up time
Signal-to-noise ratio
Calibration condition
IEC 60068-2-6 and IEC 60068-2-64
4 g/2 ... 100 Hz
Absolute accuracy
≤±0.05% of measured value
Basic accuracy
≤ ±0.1°C
≤ ±0.15°C
≤ ±1.3°C
≤ ±0.05 Ω
≤ ±10 μV
≤ ±0.5°C
≤ ±1°C
< ± 0.5°C
Standard
EN 61326
< ±0.1% of the measuring span
< ±1% of the measuring span
Operating Instructions, 06/2010, A5E01018688-02
Temperature coefficient
≤±0.002% of measured value /
°C
Temperature coefficient
≤ ±0.002°C / °C
≤ ±0.002°C / °C
≤ ±0.02°C / °C
≤ ±0.002 Ω / °C
≤ ±0.2 Ω / °C
≤ ±0.010°C / °C
≤ ±0.025°C / °C
30 s
Min. 60 dB
20 ... 28°C
SITRANS TH400