Attach the grounding cable onto the ground studs. The grounding cable
3
must comply with your local electrical codes in size and color (typically
the color is green or green with yellow stripe),
listed 2-hole lug with 1/4-inch holes on 3/4-inch spacing.
Cable Connector Required for E600i DC
High-strand-count
conductor
All measurements in inches.
Replace the two washers and nuts.
4
With a 7/16-inch box or socket wrench, tighten the nuts to 25 in-lbs.
5
Connect the opposite end of the grounding cable to the nearest
6
appropriate facility grounding post.
NOTE:
Grounding cables must be terminated only with a UL-
0.267
diameter
2 Holes
0.750"
Installing the Hardware