CONFIGURATION OF THE BM50 pLAN ADDRESS

Function
It may be necessary to change the address of the BM50 card on the pLan network – mainly in the case of Master/Slave
installation. To do this, use the following procedure:
Description
Set the address of the DS/DC50 display to 0:
Sds.1
Sds.2
Changing the address of BM50
Sds.3
Sds.4
CLIMATIC™50 – Chiller / Heat Pump – Customer version
CL50-CHILLER-IOM_CUST-0808-E
Access the configuration mode by pressing the buttons
for at least 5 seconds until the Sds.1 screen appears:
to position the cursor over the 'Setting' line
Press button
or
 button, set the address of the display to 00 (instead of the
With the
standard value of 32) and confirm with button 
The Sds.2 screen appears.
Switch the power supply to the BM50 card off, then on again after 5 seconds.
When the Sds.3 screen appears, press, the 'Alarm' and
for 5 seconds.
The Sds.4 screen appears.
to position the cursor over the 'pLan address' line. With
Press the button
 set the desired pLan address (1 to 12) and confirm with button
button
or
.

,
buttons
Page 15