CONFIGURATION OF THE BM50 pLAN ADDRESS
Function
It may be necessary to change the address of the BM50 card on the pLan network – mainly in the case of Master/Slave
installation. To do this, use the following procedure:
Description
Set the address of the DS/DC50 display to 0:
Sds.1
Sds.2
Changing the address of BM50
Sds.3
Sds.4
CLIMATIC™50 – Chiller / Heat Pump – Customer version
CL50-CHILLER-IOM_CUST-0808-E
Access the configuration mode by pressing the buttons
for at least 5 seconds until the Sds.1 screen appears:
to position the cursor over the 'Setting' line
Press button
or
button, set the address of the display to 00 (instead of the
With the
standard value of 32) and confirm with button
The Sds.2 screen appears.
Switch the power supply to the BM50 card off, then on again after 5 seconds.
When the Sds.3 screen appears, press, the 'Alarm' and
for 5 seconds.
The Sds.4 screen appears.
to position the cursor over the 'pLan address' line. With
Press the button
set the desired pLan address (1 to 12) and confirm with button
button
or
.
,
buttons
Page 15