ABB ACS850 Hardware Manual page 51

Drive modules
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

M10x25
M10
2 pcs
1
WARNING! Fasten the output busbars to the insulating supports with M10x20 screws when no
cable lug terminal is connected, but with M10x25 screws when a cable lug terminal is connected as
well. Screwing an M10x25 screw without a cable lug terminal through the busbar into the insulating
support will break the insulating support.
M10x20
Cable lug
terminal
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
M10x20
M10x25
2
2
2
2
2
2
2
Insulating support
M10x25
2
2
2
2
2
M10x25
Tightening torques:
M10: 30...44 N·m
(22...32 lbf·ft)
M12: 50...75 N·m
(37...55 lbf·ft)
Mechanical installation
51