Iq Data - Westinghouse IQ DATA User Manual

Line metering system
Table of Contents

Advertisement

TO 172838
QUICK LIST FOR IQ DATA INSTALLATION
It is suggested that you thoroughly familiarize yourself with the
IQ Data User's Manual before attempting installation. This list
should be used to assist you.
2 . Using the technical manual, pages 1 8 and 1 9, set the DIP
switches on the back of the IQ Data at the desired values
(CT ratio, PT ratio, nominal line voltage).
3. Connect the power leads to the voltage inputs of the IQ
Data- directly from the line if 600 volts or below, from PT's
for up to 1 4.4 KV.
4. Connect CT inputs to the CT terminals of the IQ Data. Be
extremely careful to connect the inputs correctly and to line
up the phases with the voltage.
5 . If not using a 3-phase Power Module, then verify that
Areas in this manual shaded in gray (
units which operate with the optional 3-phase Power Module (IQ
Data style number 2078533G03). If your unit does not have this
option, please skip these shaded areas.
jumpers are installed correctly for your application (see
Paragraph 2.1.2 , item 3, page 7). Connect the 120/2 40
VAC control power to the unit at terminals 7 and 1 0. When
Dl P switches have been verified, apply.control power to the
unit.
· · ·
·:
7. If you think a problem exists, check the voltage and current
readings with hand-held meters. If they are correct, the unit
should be operating correctly. If an LED is not functioning,
return the device to the factory for repairs.
IMPORTANT
Shaded area designates information that
replaces or supplements applications using
the 3-phase Power Module.
3
·
· · · · · .· ·
) pertain only to those
10 DATA
·
· ·
· · . ·
· ··
· ·
·
· ·
.