Specifications; Dip Switch Settings 1 - Westinghouse IQ DATA User Manual

Line metering system
Table of Contents

Advertisement

TD 172838
of the AC line voltage being monitored.
4. A neutral is provided for 4-wire systems. (Where the moni­
tored AC lines are a 3-wire configuration, this terminal
is not to be wired.) Note: This neutral connection must
be at the same potential as the ground connection used
at the current transformers.
5. DIP switches, located on the right side of the chassis,
tailor each IQ Data to a specific application . These DI P
switches are set according to characteristics such as the
external PT and CT ratios. A complete description of each
DIP switch setting is listed in Section 4.
6. A Communication Port, located on the lower right of the
chassis, is desig ned to connect with an optional Com­
munication Module (PONI Card).
· ·
·
.
. �tai� ()()ntrQI pewerls
.
.
.
.
. .
.
. · .
·
. .
.
,
'
' ' ' �
.
•.
Item
AC Amperes (2)
Voltage
Voltage
(1) Updated every 1.4 seconds with a 60 Hz line, or 1.5 seconds with a 50 Hz line, unless otherwise noted.
(2) ::!: 1% Accuracy of reading valid for currents above 20% of the CT primary rating.
·
.
.
.
.
.
·
.
·
• .
. . .
.
. . . .
·
·
·
·
. .
.
.
.
.
.
· . .
.
. .
..
.
.
.
'
'
Table 2.8
Phase A, B, C
Line A-to-B, B-to-C, and C-to-A
Line A-to-neutral, B-to-neutral , and C-to-neutral
2.1.3 External Hardware
transformers be wired into the CT Terminal Block from an
external location (See Figures 4 . 4A- 4 . 4 F).These are user­
supplied and must have a 5 ampere secondary.
Potential transformers are required when line voltage is above
600 volts. These are wired directly to the AC Line Connection
Terminals. (See Figures 4 . 4 B, 4 . 4 D and 4 . 4 F.)

2.2 Specifications-

Data are contained here:
General specifications (Table 2 . A)
Metering specifications (Table 2 . B)
GENERAL SPECIFICATIONS
Device's Power Requirement
With 3-phase Power Module
Line Characteristics
Nominal Line ± 20%
Operating Temperature
oo
to 70°C (32° to 158°F)
Storage Temperature
-20° to 85°C (-4° to 185°F)
0 to 95% R.H. noncondensing
(1) DIP switch must be set for the correct incoming frequency.
MET ERING SPECIFICAT IONS!1l
Description
9
Shaded area designates information that
replaces or supplements applications using
the 3-phase Power Module.
IQ DATA
- Each IQ Data requires current
The following specifications of the IQ
Table 2.A
PT
Burden
0.02 VA
10 VA
C.T. Burden
1. 2 5 VA
Frequency
50/60 H z ( 1 )
Humidity
Accuracy
In % of Reading
±1%
±1%
±1%