Advanced Program Group - Allen-Bradley PowerFlex 4M User Manual

Frn 1 series, frn 2 series, adjustable frequency ac drive
Table of Contents

Advertisement

Advanced Program Group

A401 [Accel Time 2]
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page 1-20
for details.
Maximum Freq
=
Accel Rate
Accel Time
Values
Default
Min/Max:
Display:
P105 [Maximum Freq]
Speed
0
P109 or A401
[Accel Time x]
0
A402 [Decel Time 2]
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on
page 1-20
for details.
Maximum Freq
=
Decel Rate
Decel Time
Values
Default
Min/Max:
Display:
P105 [Maximum Freq]
Speed
0
P109 or A401
[Accel Time x]
0
20.0 Secs
0.0/600.0 Secs
0.1 Secs
P110 or A402
Time
[Decel Time x]
20.0 Secs
0.1/600.0 Secs
0.1 Secs
P110 or A402
Time
[Decel Time x]
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Programming and Parameters
Related Parameter(s):
Related Parameter(s):
Publication 22F-UM001D-EN-E
3-19
P109
P110

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents