Electric Connection - Elwa HOTRUN 35 Operating And Fitting Instructions Manual

Electric instantaneous water heaters
Table of Contents

Advertisement

1 . Australian and New Zealand Standards wiring rules and guidelines must be adhered to .
In most situations the installation of a 2-phase supply will be required for the Hotrun 72 and
90, to avoid voltage drop on a single phase supply/connection .
2 . It is recommended to provide a dedicated circuit direct from the switchboard to each Hotrun .
3 . The Hotrun has to be connected according to the applicable wiring diagram .
4 . Check insulation resistance and proper earth continuity . Fill the unit with water, and only
then, switch the power on .
5 . The applied wiring lugs on the wires end of the flexible cords must not be removed, these
are essential to avoid arcking of the connections to the terminals . Removing the lugs voids
the warrantee on the product .
6 . Models 72 and 90 can be connected to a single phase power supply (32 resp . 40Amps) or
2-phase power supply (2x16A resp . 2 x20A) . When connecting to a single phase circuit the 2
Live wires (brown and grey) can be joined in the supplied 2-way wire lug) .
Hotrun up to 3.5 kWatt:
(single phase)
Hotrun 4.6 - 6.0 kWatt:
(single phase)

Electric connection

L1
For single phase
L2
Join L1 (brown)
and L2 (grey)
together in a lug
N1
N2
7