8. External input and output

With using external input and output functions, this product can be operated inter-connectedly
with an external device.
Connector
CN14
Control input
CN16

8-1. External input

With using external input function, some functions on this product can be controlled from an exter-
nal device.
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
¢ Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
Input
Operation status output
Initial setting after power is on
Auto changeover
76 °F (24 °C)
AUTO
Standard air direction (swing OFF)
- 17 -
Output
Starting mode other than initial
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
Remarks
See external input/output
settings for details.
setting