Gas Measuring Range Set Up - Honeywell Sensepoint XCD RTD Technical Manual

Remote toxic detector
Table of Contents

Advertisement

Sensepoint XCD RTD Technical Manual
character and repeat step 5.
7. Once all characters are selected, hold the magnet over the () switch for one
second and remove. The display will return to 'SEL GAS'.
8. Hold the magnet over the (▼) switch twice, the display will show 'QuIT'. Hold the
magnet over the () switch for one second and remove. The XCD RTD will return to
normal Monitoring mode and the new GAS NAME will be shown on the display.

9.1.2 Gas Measuring RANGE set up

Whether a Honeywell Analytics Sensepoint Toxic sensor, or an alternative type of gas
sensor is to be used with XCD RTD, the Gas Measuring Range of the sensor must be
selected manually from a pre-selected list of available measuring ranges, using the
following procedure:
1. To access the configuration menu, hold the end of the magnet over the switch
located at the top center of the XCD RTD display () for at least 3 seconds, until the
"confirm" ICON (
will indicate 'SEt CAL'
2. Hold the magnet over the (▲) switch for one second and remove. The display will
change to 'SEL GAS'.
3. Hold the magnet over the (▲) switch for one second and remove. The display will
change to 'SEt rAng'. Hold the magnet over the () switch for one second and
remove.
When a gas detector other than the Honeywell Analytics Sensepoint Toxic range of
sensors is to be used, go to step 6.
4. When using a Honeywell Analytics Sensepoint Toxic sensor the display will show
'rAng'. With the magnet, use the (▲) or (▼) switches to scroll (one at a time) through
the available choices of gas measuring range.
5. Once the desired measuring range is showing on the display, hold the magnet over
the () switch for one second and remove.
Now go to step 13.
6. When a gas detector other than the Honeywell Analytics Sensepoint Toxic range of
sensors is to be used, the display will then show 'dPnt' which means Decimal Point.
7. Now with the magnet, use the (▲) or (▼) switches to scroll (one at a time) through
the available choices of Decimal Point positions, (choose from: 1, 0.1 or 0.01).
8. Hold the magnet over the () switch for one second and remove. The display will
then show 'Low 0.0' (the '0.0' (or '0' or '0.00' part is flashing). 'Low' means the lowest
value in any given measuring range.
) shows on the LCD, and then remove the magnet. The display
29
SPXCDHMRTEN Issue 1