8. INSTALL THE CONNECTING PIPE
Safety Precautions
W ARNING
All field piping must be performed by a licensed
technician, and must comply with all local and
national regulations.
When the air conditioner is installed in a small
room, measu res must be taken to prevent the
refrigerant concentration in the room from
exceeding the safety limit, in the event of
refrigerant leakage. If the refrigerant leaks, and
its concentration exceeds its al
due to lack of oxygen may result.
When installing the refrigeration system, ensure
that air, dust, moisture or foreign substances do
not enter the refrigerant circuit. Contamination
in the system may cause poor operating capacity ,
high pressure in the refrigeration cycle, explosions,
or injuries.
Ventilate the area immediately if there is
refrigerant leakage during the installation. Leaked
refrigerant gas is both toxic and flammable.
Ensure there is no refrigerant leakage after
completing the installation work.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the number
of bends, and the drop height between the indoor and
outdoor units meets the requirements shown in Table 8.1:
lowable limit, haza
rds
Table 8.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of Model
Capacity
(Btu/hr)
12K
50Hz T1
18K-24K
Condition/R22
30K-42K
Split Type
48K-60K
50Hz Vertical
12K
Discharge, 60Hz
18K-24K
T1 condition/ R22
Split Type, Vertical
30K-60K
Discharge
12 K
18K - 24 K
R410A Inverter
Split Type
 30K - 36 K
48K - 60 K
12K
18K-30K
R410A Split Type
36K
48K-60K
18K-24K
50Hz/60Hz T3
30K
condition (outdoor
36K
unit down)
42K-60K
18K-24K
30K
50Hz/60Hz T3
Condition (outdoor
36K
unit up)
42K
48K-60K
Unit with "Quick
12K-18K
Joint"
Length of
Maximum
piping
drop height
15/49
8/26
30/98.4
10/32.8
50/164
20/65.6
50/164
25/82
15/49
8/26
30/98.4
10/32.8
30/98.4
20/65.6
25/82
10/33
30/100
20/66
50/164
25/82
65/213
30/100
15/49
8/26
25/82
15/49
30/98.4
20/65.6
50/164
25/82
35/114
10/32.8
30/98.4
15/49
30/98.4
20/65.6
50/164
25/82
25/82
15/49
30/98.4
20/65.6
30/98.4
25/82
50/164
30/98.4
50/164
35/114
5/16.4
5/16.4