Download Print this page

Siemens 9330 series Product Manual page 8

Power meter

Advertisement

9330/9350 Advanced Power Meters
Ratings
Voltage Inputs
50 to 347 VAC
25% overrange
CWC Option: Pluggable captured-
wire connectors.
All Options: Overload withstand for
1500 VAC continuous, 3250 VAC
for 1 second non recurring. Input
Impedance: > 2 MΩ
Current Inputs
5 Amp nominal / 10A full scale
Overload withstand: 20A continuous,
500A for 1 second non-recurring
Worst Case Burden (@10A):
0.0625 VA
20% Overrange full accuracy
Power Supply
Basic: 95 to 240 VAC (±10%), (47 to
440 Hz) 120 to 310 VDC (±10%),
0.2 Amp worst case loading (12W)
@ 100 VAC @ 25°C (77°F)
P24 option: 20 to 60 VDC (±10%),
0.6 A worst case loading (12W)
User Programmable Log Capacity
Example Configurations:
Event
9330
500
500
500
500
9350
500
500
500
500
A 16 parameters recorded every 15 minutes
B 16 parameters recorded hourly
7
Environmental Conditions
-20°C to +60°C (-4°F to +140°F)
ambient air
Storage: -30°C to +85°C (-22°F
to +185°F)
Humidity: 5% to 95%
non-condensing
Digital Outputs
4 Optically isolated digital outputs
Maximum forward current: 80mA
Maximum voltage: 30V
(9330 and 9350 )
Status Inputs
Self-excited, dry contact, no external
voltage source required
+30 VDC differential SCOM output
to S1 through S4 inputs
Minimum Pulse Width: 25 msec
Standards Compliance
UL: Certified to UL 3111
CAN/CSA C22.2 No.1010-1
CE marked
IEC 1010-1
Waveform Recording Settings
Data
Channel
A
B
C
D
A
6
B
6
A
6
D
6
C 4 parameters recorded every 15 minutes
D 4 parameters recorded every hour
Surge Withstand: All inputs pass
ANSI/IEEE C37.90-1989 surge
withstand and fast transient tests
FCC: Part15, FCC Rules for Class A
Digital Device
.
Samples
Cycles
per cycle
32
12
32
12
16
48
64
16
LISTED
Digital Power
Monitor
20SJ
ISO 9002-94
Registration Cert# 002188
Record
# of
depth
days
29
118
96
383
3
28
3
111
3
26
3
331

Advertisement

loading

This manual is also suitable for:

9350 series