GAS SUPPLY CONNECTIONS

Gas piping must have a sediment trap ahead
of the heater gas controls, and a manual shut-off valve
located outside the heater jacket. All gas piping should
be tested after installation in accordance with local
codes.
Sediment Trap
CAUTION: The heater and its manual shut off valve
must be disconnected from the gas supply during any
pressure testing of that system at test pressures in
excess of 1/2 psig (3.45 KPA). Dissipate test pressure
in the gas supply line before reconnecting the heater
and its manual shut off valve to gas supply line.
FAILURE TO FOLLOW THIS PROCEDURE MAY
DAMAGE THE GAS
SURED GAS VALVES ARE NOT COVERED BY
WARRANTY. The heater and
shall be leak tested before placing the appliance in
operation. Use soapy water for leak test. Do NOT
use open flame.
NOTE: Do not use teflon tape on gas line pipe thread.
A flexible sealant is recommended.
A minimum of 7" W.C. and a maximum of 14" W.C.
upstream pressure under load, and no load conditions
must be provided for natural gas or a minimum of 12"
W. C. and a maximum of 14" for propane gas.
PIPE SIZING FOR GAS CONNECTIONS
MAXIMUM EQUIVALENT PIPE LENGTH
Natural Gas 1000 BTU/ FT . 60 Specific Gravity
@ 0.5" WC Pressure Drop
Propane Gas 2500 BTU/ FT
@ 0.5" WC Pressure Drop
1/2"
MODEL
N
055B
90
200
GAS PRESSURE REGULATOR
The gas pressure regulator is preset and sealed at
4" W.C. for natural gas, and ll" W. C. for propane gas.
Between the gas valve and the burners is a l/8" pipe
plug. The pressure at this point, taken with a manome-
ter, should be about 3.7" W. C. natural gas and l0.5"
W.C. propane gas. If an adjustment is needed, remove
seal and turn adjustment screw clockwise
increase pressure or counter-clockwise
decrease pressure.
Manual Shut Off Valve
Fig. # 8156
VALVE.
OVER
PRES-
its gas connections
3
3
l.53 Specific Gravity
3/4"
P
N
200
250
Gas Pressure
Manual Shut
Gas Valve
ROBERTSHAW MV
HONEYWELL VALVE MV & IID W. C. Adjustment
P
to
to
11
Gas Pressure Test
at Gas Valve
Gas Pressure Test
at Heater
W.C Adjustment
W.C Adjustment
Fig. # 8199
W.C Adjustment
Fig. # 8081.0
Fig. # 8149.0s

Hide quick links:

Advertisement

Table of Contents
loading