7. Error Codes
To obtain the error which belongs to the Error Codes list, remember that it must be selected the
right position of the DIP-switch SW1 (See Section 4.3). Here there are two lists. It must be
chosen only one list depending on the system installed.
7.1 Intesis Codes
Error in
Error Code
Remote
Modbus
Controller
0
N/A
65535
N/A
(-1)
7.2 RAC and VRF J-II / V-II / VR-II series
Error in
Error Code
Remote
Modbus
Controller
0
00
1
01
2
02
3
03
4
04
5
05
6
06
7
07
8
08
9
09
10
0A
11
0b
12
0C
13
0d
14
0E
15
0F
17
11
18
12
19
13
20
14
21
15
22
16
23
17
24
18
25
19
26
1A
27
1b
28
1C
29
1d
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
FJ-RC-MBS-1
Error Description
No active error
Error in the communication of FJ-RC-MBS-1 or Remote Controller with
the AC unit
System
Error Description
Wired remote controller error
Indoor signal error
Indoor room temperature sensor error
Indoor room temperature sensor error
Indoor heat exchanger temperature sensor (middle) error
Indoor heat exchanger temperature sensor (middle) error
Outdoor heat exchanger temperature sensor (outlet) error
Outdoor heat exchanger temperature sensor (outlet) error
Power voltage error
Float switch operated
Outdoor temperature sensor error
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Outdoor discharge pipe temperature sensor error
Heat sink thermistor (Inverter) error
Discharge temperature error
Indoor unit EEPROM error
Indoor fan error
Indoor signal error
Outdoor EEPROM error
RAC
Compressor temperature sensor error
Inverter
Pressure switch abnormal, Pressure sensor error
and
Non
IPM protection
Inverter
CT error
Active filter error
INV voltage protection
Compressor location error
Outdoor fan error
Outdoor unit computer communication error
2-way valve temperature sensor error
User's Manual r1.9 EN
URL
http://www.intesisbox.com
Email
info@intesisbox.com
Phone
+34 938047134
20/24
Need help?
Do you have a question about the FJ-RC-MBS-1 and is the answer not in the manual?
Questions and answers