ABB Excount II User Manual page 73

Hide thumbs Also See for Excount II:
Table of Contents

Advertisement

Error
Description
code
51
Too low field probe
current
52
Too high field probe
current
61
Low leakage current
62
High leakage current
1HSA 801 080-15en EXCOUNT-II Users Manual
Suggested cause and action
The system voltage is too low to generate suf-
ficient current in the field probe in the sensor.
Check that:
a) the line is correctly energized.
b) the sensor is correctly mounted.
If none of the above are found to be the cause,
take measurements at another time.
The system voltage is too high and generating
excessive current in the field probe in the sensor.
Check that:
a) the line is correctly energized.
b) the sensor is correctly mounted.
If none of the above are found to be the cause,
take measurements at another time.
The measured leakage current is too low
(< 0.2 mA
).
peak
Check that:
a) the line is correctly energized.
b) the sensor is correctly mounted.
If none of the above are found to be the cause
take measurements at another time.
The measured leakage current is too high
(> 12 mA
).
peak
Check that:
a) the line is correctly energized.
b) the sensor is correctly mounted.
If none of the above are found to be the cause
take measurements at another time.
If the error persists the surge arrester may be
suspect.
10. Transceiver error codes
73