Alarm and Event Handling
Table 13
Objects and
AEClass
AEConfigX
AESeverityX
CondNameX
EnableX
InteractionPar.EnableX In
InhXAct
98
summarizes the Alarm and Event parameters for the Standard Library
Figure 32
illustrates the alarm and event logic.
Table 13. Summary of Alarm and Event parameters
Parameter
Direction Data type
In
In
In
In
In
In
Section 6 Program Code Issues
Dint
The class for all alarms in the
object.
Dint
Defines whether condition X
should generate an alarm or event.
Possible values are 0-4 (see
above). This parameter should be
used as a configuration parameter.
Dint
Severity for alarm condition X.
String[15] Name of the condition X. Shall
have a NLS-treated default value.
Bool
If false, the XStat (and XAct)
output is kept false and the
alarm/event generation is disabled.
Bool
Same as EnableX but controlled
from faceplate. This component is
harmonized with EnableX and
actions from the alarm list. For
example, if condition X is disabled
from the alarm list,
InteractionPar.EnableX is set to
false.
When declaring the data type for
InteractionPar, the EnableX
component must be declared with
the attribute "retain".
Bool
Inhibits the XAct output. Only
introduced for a selection of
objects.