Section 6 Program Code Issues
InteractionPar.InhXAct In
X
XStat
XEnabled
XAct
XActInh
3BSE042835-600
Table 13. Summary of Alarm and Event parameters (Continued)
Parameter
Direction Data type
Out
Out
Out
Out
Out
Bool
Same as InhXAct but controlled
from faceplate. Only introduced for
a selection of objects.
When declaring the data type for
InteractionPar, the InhXAct
component must be declared with
the attribute "retain".
Bool
Indicates active condition X. This
output is enabled as long as
AEConfigX <> 0. Example: GTH.
Bool
Indicates active condition X. This
output can be controlled via
Enable.
Bool
Indicates that the XStat and XAct
parameters are enabled. This
parameter can be used when
additional actions should be
performed at Enable/Disable.
Bool
Indicates active condition X. This
output can be controlled via
Enable and Inhibit.
Bool
Indicates that the XAct parameter
is inhibited, either from faceplate or
code. This parameter can be used
when additional actions are
wanted at Inhibit. Only introduced
for a selection of objects.
Alarm and Event Handling