4. Operation
4.2. OWA 100 Adapter connection status
Displayed
Definition
status
4
Transmitter has connected with the network
and is validating its key.
5
Transmitter has validated the key and has
made a secure connection with at least one
infrastructure node
8
The OWA 100 Adapter cannot communicate
with the HART Transmitter
20
What to do
Wait for connection. If Transmitter does not
make a connection within five minutes, see
NOT CONN in this table.
For units with radio firmware build 53 or
higher: No action required.
For units with radio firmware build 52:
Transmitter will periodically look for a
second Multinode in order to form a
redundant connection to the network. If
connected with only one Multinode Wireless
Builder will display a Secondary Multinode
Address of 0.
OWA 100 Adapter User Manual
1.
Check the wiring between OWA
100 Adapter and the HART
Transmitter
2.
Check that a 4-20mA signal is
present
3.
Using a Secondary Master confirm
that the HART Transmitter will
respond to HART messages.
September 2010