Parameters - Siemens SIMATIC S7-1500 Manual

Analog output module aq 4xu/i hf (6es7532-5nd00-0ab0)
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Parameters/address space

4.2 Parameters

4.2
Parameters
Parameters of AQ 4xU/I HF
The AQ 4xU/I HF is usually already integrated in the hardware catalog of STEP 7 (TIA
Portal). In this case, STEP 7 (TIA Portal) checks the configured properties for plausibility
during configuration.
However, you can also assign parameters to the module by means of the GSD file and the
configuration software of any provider. The module does not check the validity of the
parameterized properties until after the configuration has been loaded.
When you assign the module parameters in STEP 7, you use various parameters to specify
the module properties. The following table lists the configurable parameters. The effective
range of the configurable parameters depends on the type of configuration. The following
configurations are possible:
● Central operation with a S7-1500 CPU
● Distributed operation on PROFINET IO in an ET 200MP system
● Distributed operation on PROFIBUS DP in an ET 200MP system
When assigning parameters in the user program, use the WRREC instruction to transfer the
parameters to the module by means of data records; see chapter Parameter assignment and
structure of the parameter data record. (Page 38)
The following parameter settings for the channels are possible:
Table 4- 2
Configurable parameters and their defaults
Parameters
Diagnostics
Missing supply voltage
L+
Wire break
Short circuit to M
Underflow
Overflow
18
Range of values
Default setting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Parameter
Scope with configuration software,
assignment in
e.g., STEP 7 (TIA Portal)
RUN
Integrated in the
hardware catalog
as of STEP 7
(TIA Portal) as of
V13 or GSD file
PROFINET IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Analog Output Module AQ 4xU/I HF (6ES7532-5ND00-0AB0)
Manual, 03/2016, A5E36633205-AA
GSD file
PROFIBUS DP
Module
1)
2)
Module
2)
Module
2)
Module
2)
Module
2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents