·Heating
Items
Indoor
Ambient temp.
Outdoor
Quantity
Indoor unit
Quantity in operation
Model
Main pipe
Piping
Branch pipe
Total piping length
Indoor unit fan notch
Refrigerant volume
Total current
Volts
Indoor unit
SC (LEV1)
High pressure/Low pressure (after O/S)
(before Accumulator)
Discharge (TH1)
Heat exchanger inlet (TH5)
Accumulator
Outdoor
unit
Suction (Comp)
CS circuit (TH2)
Shell bottom (Comp)
Heat exchanger inlet
Indoor
unit
Heat exchanger outlet
OC
Outdoor unit
DB/WB
Set
m
kg
A
V
Pulse
MPa
Inlet
Outlet
˚C
- 30 -
PUHY-P200YEM-A
20.0/–
7.0/6.0
4
4
71
63
50
20
5
10
10
10
10
45
Hi
Hi
Hi
Hi
11.7
11.4
10.5
380
415
290
470
410
250
0
2.10/0.43
73
0
2
2
4
–4
33
60
34
0.28
PUHY-P250YEM-A
20.0/–
7.0/6.0
4
4
100
71
63
20
5
10
10
10
10
45
Hi
Hi
Hi
Hi
11.7
15.1
13.8
380
415
330
290
470
250
0
2.10/0.38
80
–2
0
0
2
–6
33
60
34
0.28