OPERATING PROCEDURE
11. Removing the pipe temperature/liquid thermistor (TH2)
and condenser/evaporator temperature thermistor (TH5)
(1) Remove the drain pan (Refer to procedure 10) and loosen
the 2 clamps of the coil plate. (See Photo 9)
(2) Remove the coil plate (tapping screw 4×10: 2 screws).
(3) Disconnect the pipe temperature/liquid thermistor (TH2)
and condenser/evaporator temperature thermistor (TH5)
from the holder.
12. Removing the drain pump (DP)
(1) Remove the drain pan. (Refer to procedure 10)
(2) Cut the hose band and remove the hose.
(3) Loosen the clamp of the drain pump.
(4) Remove the drain pump (tapping screw 4×10: 2 screws/2
hooks).
(5) Cut the drain pump base and lead wire fixing band. (See
Figure 5)
(6) Remove the lead wire of the drain pump from the clamp of
the drain pump base. (See Figure 5)
(7) Remove the drain pump (tapping screw: 3 screws). (See
Figure 6)
Figure 6
OCH626A
Tapping screws
42
PHOTOS & ILLUSTRATIONS
Photo 13
Pipe temperature/liquid
thermistor (TH2)
Photo 14
Drain pump
Clamp
Hose band
Drain pump base
fixing screws
Figure 5
Drain pump base and lead wire fixing band
Condenser/evaporator
temperature thermistor (TH5)
Float switch
Float switch fixing screw
Clamp of the
drain pump base