Grounding Of Protective Shields; Single Drive (Internal Power Supply) - ABB ACS580-07-0495A-4 Hardware Manual

Acs580-07 series 250 to 500 kw
Table of Contents

Advertisement

Maximum cable lengths:
300 m (984 ft) between activation switch (K) and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first drive.
Note that the voltage at the INx terminals of each drive must be at least 13 V DC to be
interpreted as "1".

Grounding of protective shields

Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.

Single drive (internal power supply)

K
OUT1
OUT2
SGND
IN1
IN2
Control unit
STO
34
+ 24 V DC
35
+ 24 V DC
36
37
38
Control logic
Safe torque off function 139
Drive
UDC+
T1/U,
T2/V,
A
T3/W
UDC-