Configuring Wiegand vs. Dataclock

MorphoAccess is configured during manufacturing to support
the Wiegand protocol. If your installation requires supporting
the Dataclock protocol, you will need to perform the following
procedure in order to configure the device to support Dataclock.
You will be taking the housing sections apart and then putting them
back together again in order to perform the configuration.
Note: MorphoAccess can support either Wiegand or
Dataclock. MorphoAccess does NOT support both protocols
simultaneously.
Note: This installation requires the device to be disconnected
from the mounting surface with the main power to the device
turned off.

Performing the Configuration

1. Remove the four visor screw caps and the four screws securing
2. Unscrew the front housing from the back housing by removing
3. Carefully separate the front and rear housing.
4. Turn the front housing upside down in order to look inside.
the visor and remove the visor.
the four screws securing the two halves together.
Note: Carefully disconnect the cables between the front and
rear housing before completely separating the two halves.
Identify the location of the bank of eight vertical jumpers on the
motherboard by looking at the picture on the next page.
Configuring Wiegand vs. Data clock
17