2. INFORMATION FOR SAFETY.

2.1. USING THIS MANUAL.

The generic documentation of the equipment is supplied in
digital format in a CD-ROM and it includes among other docu-
ments the own user's manual of the system and the document
EK266*08 concerning the
any action in the equipment as regards to installation or start
up, location change, setting or handling of any nature, read
them carefully.
The purpose of the user's manual is to provide the information
concerning the safety and the explanations of the procedures to
follow for the installation and operating of the equipment. Read
them carefully and follow the stated steps in the established
order. The identification of all parts linked with the connection
and start up by means of labels with their functionality, is corre-
lated in the instructions of this document, in order to make any
operating easy and reliable.
It is
mandatory the compliance with «Safety instruc-
tions», being the legal responsible the end user
gards to its observance and application.
Finally, once the equipment is installed and in operation, it is rec-
ommended to keep the documentation CD-ROM in a safe place
with easy access, for the future consults or doubts that could arise.
The following terms are used in the document indistinctly when
referring to:
«Bypass, panel, equipment, or unit».- To the manual by-
pass panel.
«System
or set».- Set based on one or more UPS's and the
manual bypass panel.
«T.S.S.».- Technical Service & Support.
«Client, fitter, operator or end
and extending to the fitter and/or operator, they will do the cor-
responding actions, being able to revert the responsibility of doing
the respective actions in the same person as they are acting on
behalf of himself.
In those installations with IT neutral regime, the switches
and circuit breaker protections must break the NEUTRAL
apart from the phase or phases.
2.1.1. Conventions and used symbols.
Some symbols can be used and shown in the equipment and/
or in the context of the user's manual.
For more information concerning the
see section 1.1.1 of document EK266*08.
USER'S MANUAL
instructions». Before doing
«Safety
user».- They are used indistinctly
«Safety
instructions»,
2.2. ADDITIONAL SAFETY NOTICES.
In the point of view of the installation and electrical safety,
bypass panels must be considered as transformers or
power lines of distribution.
As the equipment has protection against electrical shock of
class I, it is essential to install the protective earth cable (con-
nect the PE cable to the terminal
The bypass panel must be installed by
sonnel
only, just with help of this «User's manual».
It is important to meet the safety instructions stated in the
own «User's, installation and start manual of the UPS».
The instructions that you are reading are referred to the
own manual bypass panel only, and they are complemen-
tary to the «UPS user's manual».
The neutral regimes from the input to the output are iden-
tical for the bypass panels «with no galvanic isolation». It is
as re-
mandatory to keep the neutral regime the same, for both the
bypass panel and the UPS.
When a bypass panel has a galvanic isolation trans-
former, as an option and fitted in by the factory or in-
stalled later on by the end user, either in the input or output of
the equipment, protections against indirect contact (RCD) must
be fitted in at the output of each isolation transformer, in order
to avoid the electrical shock risk in the secondary winding
(transformer output), because due to its own nature of iso-
lating will avoid the tripping of the protections fitted in the
primary winding of the transformer.
As a reminder, all the installed isolation transformers or
those ones supplied from factory, the output neutral
connected to the PE
the neutral and PE terminals (TT regime). In case, it is re-
quired an isolated output neutral, this cable bridge must be
removed (IT regime), take all the cautions stated in the re-
spective local and/or national low voltage regulations.
In those installations with IT neutral regime, the switches
and circuit breaker protections must break the NEUTRAL
apart from the three phases.
(
)).
qualified per-
and it can be used by
trained personnel
( )
through a cable bridge between
(N)
is
5