Communication Setings Mode.
It is possible to change the device ID to be used for communication. Also
Baud rate, Parity and stop bits can also be changed from the meter. To
change the parameters:
1. Press INC switch for 3 seconds. Display will show
2. Press Next switch to Enter. Now Display will show the password
screen. Enter the password using INC switch.
3. Press Next to accept the password, Display will show
4. Now again press Next Switch to enter into confguration menu.
5. Press next switch to change the device ID.
6. Choose a device ID using INC switch from 1 to 655535.
Press Next switch for next parameter.
7. Press next switch to change the baud rate.
8. Press INC switch to choose a baud rate from 1200/2400/4800/
9600/195200. Press next switch to jump to new parameter.
9. Press next switch to change the parity seting.
10. Choose from None/Even/Odd using INC switch. Press Next
switch for next parameter.
11. Press next switch to change the Stop Bits.
12. Choose from 1 or 2. Press Next switch to save and exit.
ENTER Pa55.
123
PA55 OK.
device ID
452
Baud rate
9600
Parity
EVEN
5top Bi5
2