DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL Contents INTRODUCTION .......................4 FEATURES & OPTIONS ....................5 PRODUCT LINE .........................5 SAFETY & INDUSTRY STANDARDS ................6 WARRANTY (summary) ....................6 DESCRIPTION OF OPERATION ..................7 SPECIFICATIONS ......................8 FRONT PANEL DESCRIPTION ..................8...
Page 3
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL FIGURES Figure 1. DPG1U & DPU1U Front Views ..................4 Figure 2. Block Diagram .......................7 Figure 3. DPB1U Front Panel View ....................8 Figure 4.
Figure 1 shows the two series of panels. The first is the DPG1U Series which has 10 GMT fused circuits on both A and B sides. The second is the DPB1U Series with up to 6 circuit breaker circuits on both A and B sides.
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL FEATURES & OPTIONS The following is a summary of the important features of the Series. Thin Height: 1.75 inches (1RU) ...
God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance. For a complete text of UNIPOWER’s warranty conditions please request a copy from your local Sales Office.
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL DESCRIPTION OF OPERATION Power Distribution Circuits. A simplified schematic diagram of the distribution panels is shown in Figure 2. The battery input to each load connects to a high-current copper bus bar from which the individual fuses or circuit breakers distribute power to the loads.
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL SPECIFICATIONS The following specifications are typical at 25°C unless otherwise noted. INPUT / OUTPUT ENVIRONMENTAL Panel Capacity ........... See Panel Configuration Table Operating Temp.
401-1500-0020 Brown 401-1500-0070 Green 401-1500-0030 Gray 401-1500-0080 Red/White 401-1500-0040 White 401-1500-0090 Green/Yellow 401-1500-0050 Orange DUMMY 401-1500-0100 Table 3. GMT Fuse Values UNIPOWER recommends Bussman fuses which can be ordered using the part numbers shown. Manual No. DPB-DPG-4 dpb_dpg-man-rev4-0317.indd Page 9...
Panduit Corp., using the model numbers shown in table 4. A standard kit of four two-hole crimp type lugs for no. 6 AWG copper wire is available from UNIPOWER. Order kit no. 775-1434-0000. dpb_dpg-man-rev4-0317.indd Manual No. DPB-DPG-4...
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL WIRE .25DIA. PANDUIT CORP. UNIPOWER HOLES PART NUMBER PART NUMBER LCA8-14-L 625-1665-0010 LCD8-14A-L 625-1665-0110 LCA6-14-L 625-1665-0020...
ALARM DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL A Side Breakers Alarm LEDs B Side Breakers Form C Relay Contact Outputs. The center of the back panel has connections to the Form C relay contact outputs for connection to external audible or visual alarm circuits.
Also save the shipping carton and packing material as evidence of damage for the freight carrier’s inspection. UNIPOWER will cooperate fully in case of any shipping damage investigation. 10.3 Always save the packing materials for later use in shipping the unit. Never ship the rectifier 10.4...
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL 11.0 INSTALLATION Mounting. This distribution panel can be mounted in either 19- or 23-inch racks by using 11.1 the supplied reversible brackets.
Page 15
DPB1U & DPG1U SERIES P O W E R I N G T E C H N O L O G Y OPERATING MANUAL Checking Connections. Carefully check the polarity of input connections to the distribution 11.4 panel and output connections to the load before operating the panel. Reverse connections will not harm the distribution panel as it is POLARITY NEUTRAL.
US +1 954 346 2442 UK +44 (0)1903 768200 This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.