7.3 Condensate Drain Assembly

The condensate drain assembly is composed of a
tee, draincap, and a non return valve.
A condensate drain assembly must be installed on the
inlet side of the pump assembly if there is horizontal
venting of the pump, See Figure 16.
A seperate condensate drain on the pump dis-
charge side is required if there is vertical venting of
the pump or if
there is a vertical rise in the discharge line away
from the pump. See Figure 17.

Figure 16: Condensate Drain Assembly - Horizontal Flue

Description
Tee 100 mm (4")
Tee 150 mm (6")
Drain Cap 100 mm (4")
Drain Cap 150 mm (6")
Non-Return Valve
Part Number
01330203
01330204
02718851
02718852
C2383B
SECTION 7: P
The condensate drain assembly in the pump
discharge line can be eliminated if the discharge line
is horizontal through the wall and pitched down at
least 6 mm per 3 m (1/4" per 10'). This arrangement
will permit drainage of condensate through the
pump and outside via the horizontal (pitched) dis-
charge line.
I
V
UMP
NSTALLATION AND
ENTING
27