6 Buffer memory
6.3.4 Ior1 present value (Un \ G1150)
Stores the measured value of CH1 leak current for resistance.
For the buffer memory address of CH2, refer to section 6.1(2).
(1) Details of stored data
(a) Storage format
Data are stored as 16-bit unsigned binary in the buffer memory.
- Data range: Low sensitivity mode: 0 to 9999 (mA), High sensitivity mode; 0 to 65535 (x10
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Data update cycle
It will be updated approximately every 10 seconds.
6.3.5 Ior1 max. value (Un \ G1151)
Stores the max. value of Ior1 present value.
For the buffer memory address of CH2, refer to section 6.1(2).
(1) Details of stored data
(a) Storage format
Data are stored as 16-bit unsigned binary in the buffer memory.
- Data range: Low sensitivity mode: 0 to 9999 (mA), High sensitivity mode; 0 to 65535 (x10
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Data update cycle
It will be updated according to the update cycle of Ior1 present value (Un\G1150).
(2) How to clear the stored data
To clear all of CH1 max. values, perform the following operations.
- Change CH1 max. value clear request (YnA) from OFF to ON.
After stored data are cleared, the max. values that have been obtained since all data were cleared will
be stored for every CH1 max. value.
*To clear CH2 max. values, follow the same procedure using CH2 max. value clear request (YnC).
6 – 9
QE82LG
-2
mA)
-2
mA)