ABB DNP 670 Series Communication Protocol Manual page 55

Relion 670 series
Hide thumbs Also See for DNP 670 Series:
Table of Contents

Advertisement

1MRK 511 391-UUS A
Name
Values (Range)
tVREvBufTout1
0.00 - 60.00
UREvCntThold2
1 - 100
tVREvBufTout2
0.00 - 60.00
UREvCntThold3
1 - 100
tVREvBufTout3
0.00 - 60.00
DelOldBufFull
No
Yes
ExtTimeFormat
LocalTime
UTC
DNPToSetTime
No
Yes
tSynchTimeout
30 - 3600
TSyncReqAfTout
No
Yes
Averag3TimeReq
No
Yes
PairedPoint
No
Yes
tSelectTimeout
1.0 - 60.0
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
670 series 2.2 ANSI
Communication protocol manual
Unit
Step
Default
s
0.01
5.00
-
1
5
s
0.01
5.00
-
1
5
s
0.01
5.00
-
-
No
-
-
UTC
-
-
No
s
1
1800
-
-
No
-
-
No
-
-
Yes
s
0.1
30.0
s
1
0
s
1
10
DNP3 parameters
Description
Unsolicited response class 1 event buffer
timeout
Unsolicited response class 2 event count
report treshold
Unsolicited response class 2 event buffer
timeout
Unsolicited response class 3 event count
report treshold
Unsolicited response class 3 event buffer
timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is
generated
Time synchronization request after timeout
Use average of 3 time requests
Enable paired point
Select timeout
Broken connection timeout
Keep-Alive timer
Section 4