DNP3 parameters
Name
Values (Range)
tVREvBufTout1
0.00 - 60.00
UREvCntThold2
1 - 100
tVREvBufTout2
0.00 - 60.00
UREvCntThold3
1 - 100
tVREvBufTout3
0.00 - 60.00
DelOldBufFull
No
Yes
ExtTimeFormat
LocalTime
UTC
DNPToSetTime
No
Yes
tSynchTimeout
30 - 3600
TSyncReqAfTout
No
Yes
Averag3TimeReq
No
Yes
PairedPoint
No
Yes
tSelectTimeout
1.0 - 60.0
Table 8:
CHSEROPT Non group settings (basic)
Name
Values (Range)
BaudRate
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
57600 Bd
115200 Bd
36
Unit
Step
Default
s
0.01
5.00
-
1
5
s
0.01
5.00
-
1
5
s
0.01
5.00
-
-
No
-
-
UTC
-
-
Yes
s
1
1800
-
-
No
-
-
No
-
-
Yes
s
0.1
30.0
Unit
Step
Default
-
-
9600 Bd
1MRK 511 391-UUS A
Description
Unsolicited response class 1 event buffer
timeout
Unsolicited response class 2 event count
report treshold
Unsolicited response class 2 event buffer
timeout
Unsolicited response class 3 event count
report treshold
Unsolicited response class 3 event buffer
timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is
generated
Time synchronization request after timeout
Use average of 3 time requests
Enable paired point
Select timeout
Description
Baud-rate for serial port
670 series 2.2 ANSI
Communication protocol manual
PID-4106-SETTINGS v7

Advertisement

Table of Contents
loading