ABB DNP 670 Series Communication Protocol Manual page 53

Relion 670 series
Hide thumbs Also See for DNP 670 Series:
Table of Contents

Advertisement

1MRK 511 391-UUS A
Table 26:
MST4TCP Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SlaveAddress
0 - 65519
MasterAddres
0 - 65519
ValMasterAddr
No
Yes
MasterIP-Addr
0 - 18
MasterIPNetMsk
0 - 18
Obj1DefVar
1:BISingleBit
2:BIWithStatus
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Table continues on next page
670 series 2.2 ANSI
Communication protocol manual
Unit
Step
Default
-
-
Disabled
-
1
1
-
1
1
-
-
Yes
IP
1
0.0.0.0
Address
IP
1
255.255.255.255
Address
-
-
1:BISingleBit
-
-
3:BIChWithRelTim
e
-
-
1:DIWithoutFlag
-
-
3:DIChWithRelTim
e
-
-
2:BOStatus
-
-
5:BinCnt32WoutF
DNP3 parameters
Description
Operation Disabled/Enabled
Slave address
Master address
Validate source (master) address
Master IP-address
Master IP net mask
Object 1, default variation
Object 2, default variation
Object 3, default variation
Object 4, default variation
Object 10, default variation
Object 20, default variation
Section 4
PID-4137-SETTINGS v6
47

Advertisement

Table of Contents
loading

Table of Contents