Figure 8: Device Data Delete Dialog; Figure 9: Relay Configuration Dialog - Geist Watchdog 100 Instruction Manual

Environment monitor with output relay and optional poe
Hide thumbs Also See for Watchdog 100:
Table of Contents

Advertisement

Deleting
This device and associated data and configuration can be deleted by clicking the delete icon
confirmation prompt. The deleted device must be removed, otherwise, it will be re-detected and shown on the page.

Figure 8: Device Data Delete Dialog

Relay Control
Relay Contact Ratings
The output relay contacts are intended to carry low voltage signals only. Do not exceed the following ratings
on the output relay contacts:
DC: 60V, 30W
AC: 30Vrms, 1 A
Relay Configuration
The Watchdog 100 units provide one output relay that can be operated remotely or set to automatically open
or closed based on alarm conditions. A relay in non-latching mode will automatically energize and de-energize
as its associated alarms trip and clear. A relay in latching mode will similarly energize on an alarm trip, but will
only de-energize when acknowledged by the user on the Alarms and Warning page. See Add/Modify Alarms
and Warnings for additional information on associating an alarm condition with the output relay.
Relay Labeling and Mode Select
The relay label and manual override or alarm mode can be changed on the "Overview" page.

Figure 9: Relay Configuration Dialog

GM1118 - Watchdog 100 Series User Manual BB3.0
12
and following the
Revision Date: 12/31/2015