Mercury 2 & Intuitive Mercury EPR Stepper Installation Guide

Setup Function Menu (Common to all types)

Display
IO
View Inputs / Outputs and
States
PArA
Set/View Parameters
Unit
Probe type and
Celsius/Fahrenheit option
diSP
Display whole units or
decimal
tyPE
Set/View Controller Type
rtc
Set/view Clock (rtc = Real
Time Clock)

Recommended set-up method

If you are not connecting to a network and want to set up the controller through the buttons we recommend you use the following order
from the function menu.

rtc. Real time clock

(This will automatically synchronise on network systems)Use the up or down buttons to scroll through the display until the display reads
"rtc"
Press enter. The display will show "t-1". press enter again
a.
Scroll hours up or down (0 – 23) press enter
b.
Use up button to select "t-2", press enter
c.
Scroll minutes up or down (0 – 59) press enter
d.
Repeat for t-3 (seconds 0 – 59)
e.
f.
Repeat for t -4 (Days up to 31)
g.
Repeat for t -5 (months up to 12)
h.
Repeat for t -6 (Year up to 99)
Use up button to display "ESC", press enter to display "rtc"
i.
type. Set/view controller type
a.
From the function menu scroll to select type, press enter
b.
Use the up/down buttons to scroll through case/coldroom configuration types. (see
c.
Press enter.
Scroll to select "ESC"
d.
e.
Press enter, controller type configuration is now set.

PArA. Set/view parameters (This can be achieved at the network front end)

a.
From the function menu scroll to select PArA
b.
Pressing Enter while PArA is displayed will enter the parameter menu. The first parameter option will be displayed as P-
01. Pressing the Up or Down button will present the other parameter options P-02, P-03 etc. See the parameter list below
to find what parameter number corresponds to which actual parameter. Pressing the Enter button will show the current
value of the selected parameter. Press Up or Down to modify the value and press Enter again to save the value. The
parameter list number will be displayed again. Two other options are present in the parameter menu – dFLt and ESC.
Selecting ESC will exit setup mode. Selecting dFLt will reset all parameters back to the default values for the current type
of controller.

Unit. Set/view temperature unit and Probe type

From the function menu scroll to select Unit
Press enter and the value will be displayed: -
Probe Types
0 for PT1000 Celsius
1 for PT1000 Fahrenheit
2 for NTC2K Celsius
3 for NTC2K Fahrenheit
4 for 470R Celsius
5 for 470R Fahrenheit
6 for 700R Celsius
7 for 700R Fahrenheit
8 for 3K Celsius
9 for 3K Fahrenheit
Use the up or down keys to select the units and press enter. This function is now complete
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
Option
Explained in Paragraph
Input / output table
Set view parameters
Set View Unit
Display
Set/view controller type
Real Time Clock
10 for NTC2K25 Celsius
11 for NTC2K25 Fahrenheit
12 for 5K Celsius
13 for 5K Fahrenheit
14 for 6K Celsius
15 for 6K Fahrenheit
16 for NTC10K Celsius
17 for NTC10K Fahrenheit
18 for NTC10K(2) Celsius (USA NTC10K)
19 for NTC10K(2) Fahrenheit (USA NTC10K)
Display
nEt
Set/view network
configuration
SoFt
View software version
FAnS
Toggle Fans Only mode
CASE
Toggle Case Off mode
Ligt
Toggle Lights Only mode
OFSt
Probe Offset
ESC
Exit Setup mode
Time clock is now set
Revision 1.2a
Option
Explained in Paragraph
Network Configuration
Fans
Case Off
Lights
Probe Offset
configuration table on
page 4)
Page 9 of 25
www.resourcedm.com