Remote Commands - Resource Data Management PR0712-EPR Installation & User Manual

Mercury 2 & intuitive epr stepper valve controller
Table of Contents

Advertisement

Mercury 2 & Intuitive Mercury EPR Stepper Installation Guide

Remote Commands

The following commands can be used by a Data Builder program: -
Command
Defrost Command
Defrost Command
Trim Command
Setpoint Command
Case Off Command
Haccp Command
Button Command
EEV Command
Divider Command
Use an "Analogue Out" block configured to the
controller name and in the value field type in the
command you require. Use a "Setting block" as
the input to the "Analogue Out" block to send the
Value.
See Example on the right, which sets the Trim
Heater on BY10-1 at 40%
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
Value to send
Description
1
Initiates a defrost cycle
3
Terminates the defrost
0 to 100%
Sets the trim level to this value (Trim period is 5
minutes)
O
O
±20
C (±34
F)
Is added to or subtracted from the setpoint
5
Sets the controller to Case Off
0
Restores the controller from Case Off to Normal
0
HACCP LED OFF
1
HACCP LED On
2
HACCP LED Flashes
0
Buttons backlights Off
1
Buttons backlights On
2
Buttons Backlights Flash
2
Shuts the EPR valve
1
Restores the valve to normal operation
0 to 100%
Sets the maximum valve opening to this percentage.
Revision 1.2a
Conditions
Defrost mode: remote
Defrost mode: remote
Defrost hold: On
Defrost min state complete
Relay 4 mode: Trim Heater
Page 21 of 25
www.resourcedm.com