Mercury 2 & Intuitive Mercury EPR Stepper Installation Guide

Display

From the function menu scroll to and select diSP.
Press enter and one of the following values will be shown: -
0. Controller display will show the whole number and tenths value of a temperature reading. (Default)
1. Controller display will show temperatures as a whole number.

Parameter Tables

Not all parameters apply to all controller types, for example P-83 is Fan Control which only applies to coldroom types 5 & 6, this
parameter will not appear if the controller is set up as a type 3 or 4 case types. In the following table, the type columns on the right hand
side will be greyed out if that parameter does not apply to that controller type.
Number
Parameter
P-01
Cut-in Temp.
P-02
Diff.
P-03
Control Weight
P-04
Display Weight
P-09
Response On
P-10
Response Off
P-51
EEV Minimum Opening
P-56
EEV Start Opening
P-55
Average Valve Opening
P-57
EEV Divide Value
P-12
Relay 3 Mode
P-85
Key-switch Mode
P-87
Control Probe type
P-90
Resistor Case Off
P-92
Fans temperature mode
P-93
Fans Off Temperature
P-83
Fan Control
P-78
Fan Pulse On
P-79
Fan Pulse Off
P-15
Probe 5 Select
P-16
Relay 2 Mode
P-17
Evap. Select
P-97
Control Fail Valve Level
P-29
Probe 1 Resistor Function
P-18
Service Interval time
P-19
Switch Resistors
P-98
Lights Case Off
P-30
Valve Type
P-31
Step Max
P-32
Step Close
P-33
Step Speed
P-34
mA Peak
P-35
Half Step
P-36
mA Hold Current
P-37
Shut Speed
P-06
Shut Enable
P-07
Shut Time
P-05
Overdrive Time
P-77
Man Stop Valve/Fans
P-39
Stepper In Case Off
P-20
Alarm Delay
P-21
UT Alarm
P-22
OT Alarm
P-23
Log Probe Type
P-24
Slug Log Probe
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
Range
o
o
C
(
F )
-42 to 30 (-43.6 to 86)
0 to 10 (0 to 18)
0 to 100
0 to 100
1 to 30
1 to 30
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 = Suction Line, 1 = Defrost Valve
0 = Case, 1 = Fans only, 2 = toggle, key
off
0 = Use Air on Probe,
1 = Use Log Probe
0 (Disabled),1(Enabled)
0 = Off, 1 = Temperature,
2 = Over-temperature, 3 = Temp/OT
-42 to 30 (-43.6 to 86)
0 = Off, 1 = Run, 2 = Pulse
00:00 to 99:00
00:00 to 99:00
0 = Defrost, 1 = Monitor
0 = Lights, 1 = Alarm
0 = Local, 1 = Rem1, 2 = Rem2,
3 = Rem3, 4 = IoBrd
0 to 100%
0 = Plant fault, 1 = External defrost
0 to128
0 (Off), 1 (On)
0 (Off), 1 (On), 2 (Unused)
0=Carel, 1=Sporlan1, 2=Sporlan2
3=Alco, 4=Other*
0 to 6800 See: Valve type
0 to 6800 See: Valve type
0 to 6800 See: Valve type
0 to 500 See: Valve Type
0 (Off),1 (On) See: Valve Type
0 to 500
0 to 6800
0 (Off), 1 (On)
00:00 to 99:00
1 to 25
0 (Off),1 (On)
0 (Off),1 (On)
00:00 to 99:00
-49 to 60 (-56.2 to 140)
-49 to 60 (-56.2 to 140)
0 (Off), 1 (Logging), 2 (Logging/Alarm)
0 (Off), 1 (On)
Revision 1.2a
Step
Units
Default LT
o
o
C (
F )
0.1
Deg
-20 (-4)
0.1
Deg
2 (3.6)
1
%
50
1
%
50
1
10
1
10
1
%
10
1
%
10
1
%
100
1
50
1
1
1
3
1
0
0
1
0
0.1
Deg
-10 (14)
1
1
01:00
mm:ss
05:00
01:00
mm:ss
30:00
1
0
1
0
1
0
0.1
%
0
1
0
1
KHrs
60
1
0
1
---
0
1
---
480
1
---
500
1
Hz
50
1
mA
450
1
---
0
1
0
1
Hz
50
1
0
01:00
mm:ss
04:00
1
hours
8
1
0
1
1
01:00
mm:ss
20:00
0.1
Deg
-30 (-22)
0.1
Deg
-15 (5)
Off
Off
www.resourcedm.com
Default HT
Type
Type
o
o
C (
F )
3&4
5&6
0.0 (32)
1.5 (2.7)
50
50
10
10
10
10
100
50
1
3
0
0
0
8 (46.4)
1
05:00
30:00
0
0
0
0
0
60
1
0
0
480
500
50
450
0
0
50
0
04:00
8
0
1
20:00
-2 (28.4)
5 (41)
Off
Off
Page 10 of 25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pr0752-eprPr0713-eprPr0762-epr

Table of Contents