insTaLLaTion

PiT cHeck
1. Check entire dock leveler pit for proper construction
according to certified pit drawings (publication 5567). Check
to be sure that the pit walls are square and plumb. Prep the
pit floor for rear leveler legs. The pit should be clean and
free of any excess debris. Chip excess concrete or large
residual concrete flash left over from pouring the pit. Area
surrounding the leveling feet should be smooth and free of
excessive lumps. Check electrical service running to the
pit to assure it agrees with the correct location and voltage
for the junction box. Inspect the pit and remove all loose
trash and construction debris. Verify the pit matches pit
details for your leveler. See the installation troubleshooting
on page 14 if the pit varies from the specification.
LeVeLer cHeck Prior To insTaLLaTion
1. Visually check that the 4 rear hinge pins and retaining
clips are in place.
2. Visually check that the lip shaft collars or shaft retainers
are in place on both lip rods.
3. Verify that both the lip lock and the maintenance strut
are undamaged and the maintenance strut has a safety
hitch pin on a chain.
4. Visually check that the foot assemblies at the rear of the
leveler are in place and undamaged.
PrePare siTe
Place barricades around pit on dock floor and drive while
installing, maintaining or repairing dock leveler.
Power to control box must be from fused disconnect
supplied by others. For correct fuse size refer to wiring
diagrams on pages 15-24 of this manual. Fuses to be
class CC time delay. Before doing any electrical work,
make certain the power is disconnected and properly
tagged or locked off. All electrical work must be done
by a qualified technician and must meet all applicable
codes. If it is necessary to make troubleshooting checks
inside the control box with the power on, USE EXTREME
CAUTION. Do not place fingers or uninsulated tools inside
the control box. Touching wires or other parts inside the
control box could cause electrical shock, resulting in
death or serious injury.
1. The control station, user's manual and dock bumpers
are attached to the sub frame of the dock leveler. The
maintenance strut has a plastic tie wrap holding it to the
6
6004753N — Hydraulic Dock Leveler - One Button Control — Safe
©2014 4Front Engineered Solutions, Inc.
subframe, remove it before placing the leveler into the
pit. Make sure the customer gets the user's manual and
is properly trained.
2. Mount and wire push-button control station (See Fig.
2) and pit mounted receptacle (See Fig. 3). See wiring
diagram located on the inside cover of the control box or
wiring diagrams on pages 15-24 of this manual for wiring
information. Follow the wiring instructions to set control
for proper voltage. Wires show in dashed lines are field
connections.
3. If conduit must be installed (replacing an existing
mechanical dock leveler) do so at this time. Refer to the
conduit requirements on the pit detail publication 5567
and powered dock leveler wiring diagrams and typical
installation drawings, and powered dock leveler wiring
diagram on page 15-24 for electrical requirements.
Follow all applicable electrical codes and standards.
Fig. 2
48"
Fig. 3
Pit
center
12"
line
14"
Box located as
shown
Push-button
control station
T
Frame