DESCRIPTION
The MN307 (Cat. #2116.23) is the latest in compact AC current probes. Designed to meet the most
stringent demands in industry and electrical contracting, it also meets the latest safety and performance
standards. The probe has a measurement range up to 12Arms which make it the perfect tool for
measurements with DMMs, recorders, power and harmonic meters. The Model MN307 is compatible
with any AC voltmeter, multimeter, or other voltage measurement instrument that is capable of
displaying 100mV of output per amp of measured current, voltmeter accuracy of 0.75% or better and an
input impedance of  1M.
WARNING
The safety warnings are provided to ensure the safety of personnel and proper operation of the
instrument. Read the instruction completely.
• Use caution on any circuit: potentially high voltages and currents may be present and may pose
a shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device
before it is connected around the conductor
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III
pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the current probe is protected by double or reinforced insulation. Use
only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before
using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from
HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES
CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately
with the carrier and notify your distributor at once, giving a detailed description of any damage.

Advertisement

loading

Summary of Contents for AEMC MN307

  • Page 1 User Manual DESCRIPTION The MN307 (Cat. #2116.23) is the latest in compact AC current probes. Designed to meet the most stringent demands in industry and electrical contracting, it also meets the latest safety and performance standards. The probe has a measurement range up to 12Arms which make it the perfect tool for measurements with DMMs, recorders, power and harmonic meters.
  • Page 2 .83" (21 mm) (18.5 mm) Tactical Barrier (keep hands below this barrier) Black 2.00" (51 mm) MN307 .1.18" (30 mm) Phase Shift: ELECTRICAL SPECIFICATIONS .01 to 0.1A: Not Specified  5° 0.1 to 1A: Nominal Range: 10A  3° 1 to 5A: ...
  • Page 3: Safety Specifications

    Magnetic field at 50/60 Hz IEC 1000-4-8 (without roll-off above 35°C) Maximum Cable Diameter: ORDERING INFORMATION One Ø 0.78" (20mm), bus bar 20 x 5mm AC Current Probe MN307 ....Cat #2116.23 Case Protection: IP 40 (IEC 529) Accessories: Banana plug adapter Drop Test: (to non-recessed plug) .......
  • Page 4 This warranty is void if the unit has been tampered ® with, abused or if the defect is related to service not performed by AEMC Instruments. Full warranty coverage and product registration is available on our website at: www.aemc.com/warranty.html...