Connect Uponor Smatrix Base Pro Controller; Lv Connect Modbus Rtu Interface - Uponor Smatrix Move PRO Installation And Operation Manual

Heating/cooling application
Hide thumbs Also See for Smatrix Move PRO:
Table of Contents

Advertisement

UK
5.13 Connect Uponor Smatrix Base PRO
controller
CZ
The controller can be connected to an Uponor Smatrix
Base PRO system bus for integration with Base PRO
DE
controllers and thermostats.
The illustration below shows the Uponor Smatrix Base
Pro system bus connected to the controller.
DK
X-159
EE
-
A
B
ES
21
22
23
FI
FR
A
B
-
A
B
X-147
HR
HU
IT
W
!
arning
Electrical installation and service behind
secured 230 V AC covers must be carried
LT
out under the supervision of a qualified
electrician.
LV
To connect an Uponor Smatrix Base PRO system bus to
the controller:
1. Ensure that the power is disconnected from all
NL
controllers.
2. Remove the terminal cover on the Move PRO
NO
controller.
See section 5.6 Terminal cover for more information.
3. Remove the cover on (one of) the Base PRO
PL
controllers.
See Uponor Smatrix Base PRO documentation for
more information.
PT
RO
RU
SE
SK
4 0
-
A
B
21
22
23
-
A
B
-
A
B
-
4. Study the wiring diagrams of both controllers to
locate the connection terminal positions.
5. Connect the wires from the Base PRO controller to
the Move PRO controller.
Uponor Smatrix Base PRO:
Communication wire to system bus terminal A, B
and -.
Uponor Smatrix Move PRO:
Communication wire to system bus terminal 21
(-), 22 (A) and 23 (B).
6. Tighten the screws fixing the wires to the connector.
Enable the Move PRO controller in the Smatrix Base
PRO interface I-147:
7. Go to the Integration menu (Main menu >
Integration).
8. Press Supply Water Controller: Disable.
9. Press Enable to activate communication between
the interface and the Move PRO controller.
10. Assign controllers at the end of the Startup
Wizard in the Move PRO controller. Connected
Smatrix Base PRO controllers will be shown in a list
automatically.
See section 5.14 Startup wizard for more
information.
5.14 Connect Modbus RTU interface
The controller can be connected and integrated to
a building management system (BMS) through a
Modbus-RTU interface over RS-232.
See separate documentation for more information about
BMS integration.