Products Solutions Services BA01062D/06/EN/02.13 71218251 Valid as of version 01.00.zz (Device firmware) Operating Instructions Proline Promag L 400 HART Electromagnetic flowmeter...
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these Instructions. Endress+Hauser...
Proline Promag L 400 HART Table of contents Table of contents 6.2.2 Preparing the measuring device ..24 Document information ....6 6.2.3 Mounting the sensor .
Page 5
Proline Promag L 400 HART Table of contents 14.5 Disposal ......14.5.1 Removing the measuring device ..129 14.5.2 Disposing of the measuring device .
Document information Proline Promag L 400 HART Document information Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Proline Promag L 400 HART Document information 1.2.3 Tool symbols Symbol Meaning Torx screwdriver A0013442 Phillips head screwdriver A0011219 Open-ended wrench A0011222 1.2.4 Symbols for certain types of information Symbol Meaning Allowed Indicates procedures, processes or actions that are allowed.
The following document types are available: • On the CD-ROM supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download For a detailed list of the individual documents along with the documentation code (→...
‣ Observe the specified pressure and temperature range. Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any Endress+Hauser...
If a plastic transmitter housing is permanently exposed to certain steam and air mixtures, this can damage the housing. ‣ If you are unsure, please contact your Endress+Hauser Sales Center for clarification. ‣ If used in an approval-related area, observe the information on the nameplate.
IT security measures in line with operators' security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves. Endress+Hauser can be contacted to provide support in performing this task. Endress+Hauser...
Product description Proline Promag L 400 HART Product description Product design A0017218 1 Important components of the compact version Display module Smart sensor electronics module HistoROM DAT (plug-in memory) Main electronics module Terminals (screw terminals, some available as plug-in terminals)
Proline Promag L 400 HART Incoming acceptance and product identification Incoming acceptance and product identification Incoming acceptance A0015502 A0013843 Is the order code on the delivery note (1) identical to the order code on the product sticker (2)? A0013695 A0015502...
Incoming acceptance and product identification Proline Promag L 400 HART If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note •...
Proline Promag L 400 HART Incoming acceptance and product identification 4.2.2 Sensor nameplate Order Code: Ser.No.: Ext. ord. cd.: Material: Patents Date: A0017186 3 Example of sensor nameplate Name of the sensor Manufacturing location Order code Serial number (Ser. no.) Extended order code (Ext.
Incoming acceptance and product identification Proline Promag L 400 HART 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation.
Proline Promag L 400 HART Storage and transport Storage and transport Storage conditions Observe the following notes for storage: • Store in the original packaging to ensure protection from shock. • Do not remove protective covers or protective caps installed on process connections.
Storage and transport Proline Promag L 400 HART 5.2.2 For measuring devices ≥ DN 350 (14") Also observe the following notes during transport: • Lift the measuring device by the flange using the metal brackets. • If transporting by forklift, do not lift the sensor by the metal casing. This would buckle the casing and damage the internal magnetic coils.
Proline Promag L 400 HART Installation Installation Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe elbow: h ≥...
Page 20
Installation Proline Promag L 400 HART Installation in partially filled pipes A partially filled pipe with a gradient necessitates a drain-type configuration. The empty pipe detection (EPD) function offers additional protection by detecting empty or partially filled pipes. • Do not install the sensor at the lowest point in the drain: risk of solids accumulating.
Page 21
Proline Promag L 400 HART Installation A0015591 Horizontal The measuring electrode plane must be horizontal. This prevents brief insulation of the two measuring electrodes by entrained air bubbles. With horizontal orientation, empty pipe detection only works if the transmitter housing is pointing upwards as otherwise there is no guarantee that the empty pipe detection function will actually respond to a partially filled or empty measuring tube.
• Avoid direct exposure to weather conditions. • Protect the display against impact. • Protect the display from abrasion by sand in desert areas. A display protector can be ordered from Endress+Hauser: "Accessories" section (→ 131) System pressure • Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and thus damage to the liner.
Proline Promag L 400 HART Installation A0016266 6 Measures to prevent vibration of the device > 10 m (33 ft) Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids.
Installation Proline Promag L 400 HART Mounting the measuring device 6.2.1 Required tools For transmitter • Torque wrench • For wall mounting: Open-ended wrench for hexagonal screw max. M5 • For pipe mounting: – Open-ended wrench AF 8 – Phillips head screwdriver PH 2 •...
Page 25
Proline Promag L 400 HART Installation Mounting the seals CAUTION An electrically conductive layer could form on the inside of the measuring tube! Risk of measuring signal short circuit. ‣ Do not use electrically conductive sealing compounds such as graphite.
Installation Proline Promag L 400 HART A separate mounting kit can be ordered from Endress+Hauser for pipe mounting (→ 131). 6.2.5 Turning the transmitter housing To provide easier access to the display module in the compact device version, the...
Proline Promag L 400 HART Installation 4 mm A0021605 1. Loosen the fixing screws of the housing cover. 2. Open the housing cover. 3. Unlock the display module. 4. Remove the display module. 5. Loosen the fixing screws of the smart sensor electronics module.
Installation Proline Promag L 400 HART TX 20 A0021617 1. Loosen the fixing screws of the housing cover. 2. Open the housing cover. 3. Unlock the display module. 4. Pull out the display module and turn it to the desired position in increments of 90°.
Proline Promag L 400 HART Electrical connection Electrical connection The measuring device does not have an internal circuit breaker. For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Page 34
Electrical connection Proline Promag L 400 HART Capacitance: core/shield ≤420 pF/m (128 pF/ft) Operating temperature –20 to +80 °C (–68 to +176 °F) Coil current cable Standard cable (18 AWG) with common, braided copper shield ( ~ 7 mm (0.28")) 2 ×0.75 mm...
Proline Promag L 400 HART Electrical connection 7.1.6 Preparing the connecting cable for the remote version When terminating the connecting cable, pay attention to the following points: • In the case of electrode cables, make sure that the ferrules do not touch the core shields on the sensor side.
Proline Promag L 400 HART Electrical connection 6. Firmly tighten the cable glands. 7. WARNING! Housing degree of protection voided due to insufficient sealing of the housing. Screw in the screw without using any lubricant. The threads on the cover are coated with a dry lubricant.
Page 42
Electrical connection Proline Promag L 400 HART 1. Connect both sensor flanges to the pipe flange via a ground cable and ground them. 2. If DN ≤ 300 (12"): Mount the ground cable directly on the conductive flange coating of the sensor with the flange screws.If DN ≥ 350 (14"): Mount the ground cable directly on the metal transport bracket.Observe torques (→...
Proline Promag L 400 HART Electrical connection – A0016319 17 Potential equalization and cathodic protection Isolation transformer power supply Electrically isolated from the pipe Capacitor Ground cable Copper wire, at least 6 mm (0.0093 in 1. Connect the measuring device to the power supply such that it is floating in relation to the protective ground.
Electrical connection Proline Promag L 400 HART Ensuring the degree of protection 7.4.1 Degree of protection IP66/67, Type 4X enclosure The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1.
Proline Promag L 400 HART Operation options Operation options Overview of operation options A0015607 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX100 Field Communicator 475 Control system (e.g.
Operation options Proline Promag L 400 HART Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu with menus and parameters (→ 157) Operating menu for operators and maintenances...
Proline Promag L 400 HART Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles. Each user role corresponds to typical tasks within the device lifecycle. Menu User role and tasks Content/meaning...
Operation options Proline Promag L 400 HART Access to the operating menu via the local display 8.3.1 Operational display X X X X X X X 1120.50 A0016502 Operational display Device tag (→ 71) Status area Display area for measured values (4-line) Operating elements (→...
Page 49
Proline Promag L 400 HART Operation options Display area In the display area, each measured value is prefaced by certain symbol types for further description: Measured variable Measurement channel Diagnostic behavior number ↓ ↓ ↓ Example A0013962 A0013945 A0013948 Appears only if a diagnostics event is present for this measured variable.
Operation options Proline Promag L 400 HART 8.3.2 Navigation view In the submenu In the wizard /../Operation 0091-1 /../Curr. output 1 Access stat.disp Assign curr. Operator Volume flow Locking status Display A0013993-EN A0016327-EN Navigation view Navigation path to current position...
Page 51
Proline Promag L 400 HART Operation options Display area Menus Symbol Meaning Operation Appears: • In the menu next to the "Operation" selection A0013973 • At the left in the navigation path in the "Operation" menu Setup Appears: • In the menu next to the "Setup" selection A0013974 •...
Operation options Proline Promag L 400 HART 8.3.3 Editing view Numeric editor Text editor A0013941 A0013999 Editing view Display area of the entered values Input mask Operating elements (→ 53) Input mask The following input symbols are available in the input mask of the numeric and text editor:...
Proline Promag L 400 HART Operation options Selection of letters from a to z. abc _ … A0019094 Selection of special characters. "'^ _ … ~& A0019095 Confirms selection. A0013985 Switches to the selection of the correction tools. A0013987 Exits the input without applying the changes.
Operation options Proline Promag L 400 HART Meaning Enter key For operational display • Pressing the key briefly opens the operating menu. • Pressing the key for 2 s opens the context menu. In a menu, submenu • Pressing the key briefly: –...
Page 55
Proline Promag L 400 HART Operation options The context menu is closed and the operational display appears. Calling up the menu via the context menu 1. Open the context menu. 2. Press to navigate to the desired menu.
Operation options Proline Promag L 400 HART 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
Proline Promag L 400 HART Operation options Navigation path "Expert" menu → Direct access The direct access code consists of a 4-digit number and the channel number, which identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this appears on the right-hand side in the header of the selected parameter.
Operation options Proline Promag L 400 HART 8.3.9 Changing the parameters For a description of the editing display - consisting of text editor and numeric editor - with symbols (→ 52), for a description of the operating elements (→ 53) Example: Changing the tag name in the "Tag description"...
Proline Promag L 400 HART Operation options Ent. access code Invalid or out of range input value Min:0 Max:9999 A0014049-EN 8.3.10 User roles and related access authorization The two user roles "Operator" and "Maintenance" have different write access to the parameters if the customer defines a user-specific access code.
Operation options Proline Promag L 400 HART A0016215-EN After disabling the keypad lock: A0016216-EN If the user attempts to access the operating menu while the keylock is enabled, the message Keylock on also appears. Access to the operating menu via the Web browser 8.4.1...
Proline Promag L 400 HART Operation options When installing a new firmware version: To enable correct data display, clear the temporary memory (cache) of the Web browser under Internet options. 8.4.3 Establishing a connection Configuring the Internet protocol of the computer IP address 192.168.1.XXX;...
Operation options Proline Promag L 400 HART If no action is performed for 10 minutes, the Web browser automatically returns to the login page. 8.4.5 User interface A0017757-EN Picture of device Function row with 6 functions Device tag Header Working area...
Proline Promag L 400 HART Operation options Working area Depending on the selected function and the related submenus, various actions can be performed in this area: • Configuring parameters • Reading measured values • Calling up help text • Starting an upload/download 8.4.6...
Operation options Proline Promag L 400 HART 8.5.1 Connecting the operating tool Via HART protocol A0017124 21 Options for remote operation via HART protocol Control system (e.g. PLC) Field Communicator 475 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
Operation options Proline Promag L 400 HART User interface Xxxxx Xxxxx A0021053-EN Header Picture of device Device tag (→ 71) Status area with status signal (→ 114) Display area for current measured values (→ 102) Event list with additional functions such as save/load, events list and document creation...
Proline Promag L 400 HART Operation options 8.5.6 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol. Source for device description files See data (→ 68)
System integration Proline Promag L 400 HART System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.04.00 • On the title page of the Operating instructions • On transmitter nameplate(→ 14) • Parameter firmware version Diagnostics →...
Proline Promag L 400 HART System integration The assignment of the measured variables to the dynamic variables can be modified and assigned as desired via local operation and the operating tool using the following parameters: • Expert → Communication → HART output → Output → Assign PV •...
Commissioning Proline Promag L 400 HART Commissioning 10.1 Function check Before commissioning the device, make sure that the post-installation and post- connection checks have been performed. • "Post-installation check" checklist (→ 32) • "Post-connection check" checklist (→ 44) 10.2...
Proline Promag L 400 HART Commissioning X X X X X X X 20.50 0104-1 Main menu Language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Status input XXXXXXXXX XXXXXXXXX A0017444-EN 23 Illustrated using the example of the local display Overview of the wizards in the "Setup"...
Commissioning Proline Promag L 400 HART Navigation "Setup" menu → Device tag Parameter overview with brief description Parameters Description User entry Factory setting Device tag Enter tag for measuring point. Max. 32 characters, such as Promag letters, numbers or special characters (e.g.
Proline Promag L 400 HART Commissioning 10.4.3 Configuring the current output The "Current output 1 to 2" wizard guides you systematically through all the parameters that have to be set for configuring the particular current output. Navigation "Setup" menu → Current output 1 to 2 Structure of the wizard Assign curr.
Commissioning Proline Promag L 400 HART Parameter overview with brief description Parameters Description Selection / User entry Factory setting Assign current output Select process variable for current output. • Off Volume flow • Volume flow • Mass flow • Flow velocity • Conductivity •...
Page 75
Proline Promag L 400 HART Commissioning Structure of the wizard for the pulse output Operating mode Pulse Assign pulse Volume flow Mass flow Volume unit Mass unit Density unit Fixed density Value per pulse Pulse width Failure mode Invert outp.sig.
Page 76
Commissioning Proline Promag L 400 HART Parameters Description Selection / User entry Factory setting Density unit Select density unit. Unit choose list Country-specific: • kg/l Result • lb/ft³ The selected unit applies for: • Output • Simulation process variable • Density adjustment (in Expert menu) Fixed density Enter fixed value for medium density.
Page 77
Proline Promag L 400 HART Commissioning Structure of the wizard for the frequency output Operating mode Frequency Assign freq. Volume flow Conductivity Mass flow Volume unit Conductiv. unit Mass unit Density unit Fixed density Min. freq. value Max. freq. value Val.
Page 78
Commissioning Proline Promag L 400 HART Parameters Description Selection / User entry Factory setting Volume flow unit Select volume flow unit. Unit choose list Country-specific: • l/h Result • gal/min (us) The selected unit applies for: • Output • Low flow cut off •...
Page 79
Proline Promag L 400 HART Commissioning Structure of the wizard for the switch output Operating mode Switch Switch out funct Diag. behavior Assign diag. beh Alarm or Warning Alarm warning Invert outp.sig. End of wizard A0017439-EN 28 "Pulse/frequency/switch output 1-2" wizard in the "Setup" menu: "Switch" operating mode (Part 1)
Page 80
Commissioning Proline Promag L 400 HART Operating mode Switch Switch out funct Fl. direct. Limit Status check Assign Assign Assign limit dir.check status Conduc- Empty Volume Mass Totalizer Volume Mass Low flow tivity pipe det. flow flow 1/2/3 flow flow...
Proline Promag L 400 HART Commissioning Parameters Description Selection / User entry Factory setting Assign limit Select process variable for limit function. • Off Volume flow • Volume flow • Mass flow • Flow velocity • Conductivity • Totalizer 1 • Totalizer 2 •...
Page 82
Commissioning Proline Promag L 400 HART Structure of the wizard Format display Value 1 display 0% bargraph value 1 100% bargraph value 1 Value 2 display Value 3 display 0% bargraph value 3 100% bargraph value 3 Value 4 display...
Proline Promag L 400 HART Commissioning Parameters Description Selection / User entry Factory setting Value 3 display Select the measured value that is shown on Picklist (see 1st display value) None the local display. 0% bargraph value 3 Enter 0% value for bar graph display.
Commissioning Proline Promag L 400 HART Parameter overview with brief description Parameters Description Selection / User entry Factory setting Capture mode Select capture mode via burst or master • Off communication. • Burst network • Master network Manufacturer ID Enter manufacture ID of external device.
Page 85
Proline Promag L 400 HART Commissioning Structure of the wizard Display damping Damping out. 1 Damping out. 2 Damping out. 3 Assign curr. Volume flow Conductivity Mass flow Assign pulse Volume flow Mass flow Assign freq. Volume flow Conductivity Mass flow...
Commissioning Proline Promag L 400 HART Parameters Description User entry / Selection Factory setting Assign current output Select process variable for current output. • Off Volume flow • Volume flow • Mass flow • Flow velocity • Conductivity • Electronic temperature Assign pulse output Select process variable for pulse output.
Page 87
Proline Promag L 400 HART Commissioning Parameter overview with brief description Parameters Description Selection / User entry Factory setting Assign process variable Select process variable for low flow cut off. • Off Volume flow • Volume flow • Mass flow On value low flow cutoff Enter on value for low flow cut off.
Commissioning Proline Promag L 400 HART 10.4.9 Configuring empty pipe detection The Empty pipe detection wizard guides you systematically through all the parameters that have to be set for configuring the low flow cut off. Navigation "Setup" menu → Empty pipe detection Structure of the wizard Empty pipe det.
Page 89
Proline Promag L 400 HART Commissioning Structure of the wizard Empty pipe det. New adjustment Cancel Empty pipe adj. Full pipe adjust. Progress Busy Not ok Switch point EPD Response time End of wizard A0017210-EN 35 "Empty pipe detection" wizard in the "Setup" menu...
Commissioning Proline Promag L 400 HART 10.5 Advanced settings The Advanced setup submenu with its submenus contains parameters for specific settings. "Setup" menu → Advanced setup Navigation to the "Advanced setup" submenu X X X X X X X 20.50...
Proline Promag L 400 HART Commissioning 10.5.1 Setting the system units In the System units submenu the units of all the measured values can be set. Navigation "Setup" menu → System units System units → Volume flow unit Volume unit...
Commissioning Proline Promag L 400 HART Parameters Description Selection Factory setting Density unit Select density unit. Unit choose list Country-specific: • kg/l Result • lb/ft³ The selected unit applies for: • Output • Simulation process variable • Density adjustment (in Expert menu) Corrected volume flow unit Select corrected volume flow unit.
Page 93
Proline Promag L 400 HART Commissioning Parameter overview with brief description Parameters Description Selection Factory setting Assign process variable Select process variable for totalizer. • Off Volume flow • Volume flow • Mass flow Unit totalizer Select process variable totalizer unit.
Commissioning Proline Promag L 400 HART 10.5.4 Carrying out additional display configurations In the "Display" submenu you can set all the parameters involved in the configuration of the local display. Navigation "Setup" menu → Advanced setup → Display Structure of the submenu Display →...
Page 95
Proline Promag L 400 HART Commissioning Parameter overview with brief description Parameters Description Selection / User entry Factory setting Format display Select how measured values are shown on • 1 value, max. size 1 value, max. size the display. • 1 bargraph + 1 value •...
Commissioning Proline Promag L 400 HART Parameters Description Selection / User entry Factory setting Display language Set display language. • English English • Deutsch • Français • Español • Italiano • Nederlands • Portuguesa • Polski • русский язык (Russian) • Svenska •...
Proline Promag L 400 HART Commissioning Parameter overview with brief description Parameters Description Selection / User entry / User Factory setting interface Electrode cleaning circuit Enable the cyclic electrode cleaning circuit. • Off • On ECC duration Enter the duration of electrode cleaning in 0.01 to 30 s...
Commissioning Proline Promag L 400 HART Parameter overview with brief description Parameters Prerequsite Description Selection / User Factory setting entry Assign simulation process variable – Select a process variable for • Off the simulation process that is • Volume flow activated. • Mass flow •...
Proline Promag L 400 HART Commissioning 10.7.1 Write protection via access code The effects of the customer-specific access code are as follows: • Via local operation, the parameters for the measuring device configuration are write- protected and their values can no longer be changed.
Commissioning Proline Promag L 400 HART If no action is performed for 10 minutes, the Web browser automatically returns to the login page. The user role with which the user is currently logged on via the Web browser is indicated by the Access status tooling parameter. Navigation path: Operation →...
Page 101
Proline Promag L 400 HART Commissioning 3. WARNING! Excessive tightening torque applied to the fixing screws! Risk of damaging the plastic transmitter. Tighten the fixing screws as per the tightening torque (→ 30). Reverse the removal procedure to reassemble the transmitter.
Operation Proline Promag L 400 HART Operation 11.1 Reading device locking status The write protection types that are currently active can be determined using the "Locking status" parameter. "Operation" menu → Locking status Function scope of "Locking status" parameter Options...
Proline Promag L 400 HART Operation Structure of the submenu Parameter overview with brief description Parameters Description User interface Volume flow Displays the volume flow currently measured. Signed floating-point number Mass flow Displays the mass flow currently calculated. Signed floating-point number Conductivity Displays the corrected volume flow currently calculated.
Operation Proline Promag L 400 HART Structure of the submenu Input values → Value status input Parameter overview with brief description Parameters Description User interface Factory setting Value status input Displays the current input signal level. • High • Low 11.4.4...
Proline Promag L 400 HART Operation 11.5 Adapting the measuring device to the process conditions The following are available for this purpose: • Basic settings using the Setup menu(→ 70) • Advanced settings using the Advanced setup submenu(→ 90) 11.6...
Operation Proline Promag L 400 HART 11.6.2 Function scope of "Reset all totalizers" parameter Options Description Reset + totalize Resets all totalizers to 0 and restarts the totaling process. This deletes all the flow values previously totalized. 11.7 Showing data logging In the device, the extended function of the HistoROM must be enabled (order option) so that the "Data logging"...
Page 107
Proline Promag L 400 HART Operation Parameter overview with brief description Parameters Description Selection / User entry Factory setting Assign channel 1 Assign process variable to logging channel. • Off • Volume flow • Mass flow • Conductivity • Electronic temperature • Current output 1 Assign channel 2 Assign process variable to logging channel.
Diagnostics and troubleshooting Proline Promag L 400 HART Diagnostics and troubleshooting 12.1 General troubleshooting For local display Problem Possible causes Remedy Local display dark and no output Supply voltage does not match that Apply the correct supply voltage signals specified on the nameplate.
Proline Promag L 400 HART Diagnostics and troubleshooting For access Problem Possible causes Remedy No write access to parameters Hardware write protection enabled Set the write protection switch on the main electronics module to the OFF position (→ 100).
Page 110
Diagnostics and troubleshooting Proline Promag L 400 HART Color Meaning Flashing orange Activity present Communication Flashing white HART communication is active. Alarm Green Measuring device is ok Flashing green Measuring device not configured Firmware error Main error Flashing red Error...
Proline Promag L 400 HART Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition...
Page 112
Diagnostics and troubleshooting Proline Promag L 400 HART Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. A0013961 • The background lighting changes to red.
Proline Promag L 400 HART Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
Diagnostics and troubleshooting Proline Promag L 400 HART 12.4 Diagnostic information in the Web browser 12.4.1 Diagnostic options Any faults detected by the measuring device are displayed in the Web browser on the home page once the user has logged on.
Proline Promag L 400 HART Diagnostics and troubleshooting 12.5 Diagnostic information in FieldCare 12.5.1 Diagnostic options Any faults detected by the measuring device are displayed on the home page of the operating tool once the connection has been established. XXXXXXXX...
Diagnostics and troubleshooting Proline Promag L 400 HART 12.5.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly: • On the home page Remedy information is displayed in a separate field below the diagnostics information.
Proline Promag L 400 HART Diagnostics and troubleshooting Diagnostic information The fault can be identified using the diagnostic information. The short text helps you by providing information about the fault. In addition, the corresponding symbol for the diagnostic behavior is displayed in front of the diagnostic information on the local display.
Page 118
Diagnostics and troubleshooting Proline Promag L 400 HART You can assign the following options to the diagnostic number as the diagnostic behavior: Options Description Alarm Measurement is interrupted. Signal outputs and totalizers assume the defined alarm condition. A diagnostic message is generated.
Proline Promag L 400 HART Diagnostics and troubleshooting 12.8 Overview of diagnostic information The amount of diagnostic information and the number of measured variables affected increase if the measuring device has one or more application packages. Status Diagnostic Diagnostic signal...
Page 120
Diagnostics and troubleshooting Proline Promag L 400 HART Status Diagnostic Diagnostic signal behaviour Short text Repairing action number from the from the factory factory Data storage 1. Restart device Alarm 2. Contact service Memory content 1. Transfer data or reset device Alarm 2.
Page 121
Proline Promag L 400 HART Diagnostics and troubleshooting Status Diagnostic Diagnostic signal behaviour Short text Repairing action number from the from the factory factory Simulation pulse output Deactivate simulation pulse output Warning Switch output Deactivate simulation switch output Warning simulation...
Diagnostics and troubleshooting Proline Promag L 400 HART Status Diagnostic Diagnostic signal behaviour Short text Repairing action number from the from the factory factory Wet steam detection 1. Check pressure, temperature Warning uncertain 2. Check flow velocity 3. Check for flow fluctuation Input signal 1.
Proline Promag L 400 HART Diagnostics and troubleshooting 12.10 Diagnostic list In the Diagnostic list submenu, up to 5 currently pending diagnostic events can be displayed along with the related diagnostic information. If more than 5 diagnostic events are pending, the events with the highest priority are shown on the display.
Diagnostics and troubleshooting Proline Promag L 400 HART To call up the measures to rectify a diagnostic event: • Via local display (→ 113) • Via Web browser (→ 114) • Via "FieldCare" operating tool (→ 116) For filtering the displayed event messages (→...
Proline Promag L 400 HART Diagnostics and troubleshooting Info number Info name I1398 CDI: access status changed I1444 Device verification passed I1445 Device verification failed I1446 Device verification active I1447 Record application reference data I1448 Application reference data recorded I1449 Recording application ref.
Page 126
Diagnostics and troubleshooting Proline Promag L 400 HART Order code Extended order code 1 Extended order code 2 Extended order code 3 ENP version Device revision Device ID Device type Manufacturer ID IP address Subnet mask Default gateway Parameter overview with brief description...
"Manufacturer' s information" document. The manufacturer' s information is available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download • Specify the following details: –...
Replacement seals (accessory) (→ 156) 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. For a list of some of the measuring and test equipment, refer to the "Accessories"...
• Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by correspondingly trained customers. • Certified devices can be converted into other certified devices by Endress+Hauser Service or at the factory only. Notes for repair and conversion For repair and modification of a measuring device, observe the following notes: •...
Repair Proline Promag L 400 HART 2. WARNING! Danger to persons from process conditions. Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids. Carry out the mounting and connection steps from the chapters "Mounting the measuring device"...
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Proline Promag L 400 HART Technical data Technical data 16.1 Application The measuring device described in these Instructions is intended only for flow measurement of liquids with a minimum conductivity of 5 μS/cm. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
Page 134
Technical data Proline Promag L 400 HART Nominal Recommended Factory settings diameter flow Full scale value current min./max. full scale value Pulse value Low flow cut off output (v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s) (v ~ 2.5 m/s)
Page 135
Proline Promag L 400 HART Technical data Nominal Recommended Factory settings diameter flow Full scale value current min./max. full scale value Pulse value Low flow cut off output (v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s) (v ~ 2.5 m/s)
Technical data Proline Promag L 400 HART Input signal Status input Maximum input values • DC 30 V • 6 mA Response time Adjustable: 5 to 200 ms Input signal level • Low signal: DC –3 to +5 V • High signal: DC 12 to 30 V Assignable functions •...
Page 137
Proline Promag L 400 HART Technical data Pulse/pause ratio Assignable measured • Volume flow variables • Mass flow • Flow velocity • Conductivity • Electronics temperature Switch output Switching behavior Binary, conductive or non-conductive Switching delay Adjustable: 0 to 100 s...
Technical data Proline Promag L 400 HART Failure mode Choose from: • Actual value • Defined value: 0 to 12 500 Hz • 0 Hz Switch output Failure mode Choose from: • Current status • Open • Closed Local display...
Page 139
Proline Promag L 400 HART Technical data Supply voltage Transmitter Order code for "Power supply" Terminal voltage Frequency range AC100 to 240 V 50/ 60 Hz, ±4 Hz Option L AC/DC24 V 50/ 60 Hz, ±4 Hz Power consumption Order code for Maximum "Output"...
Technical data Proline Promag L 400 HART 16.6 Performance characteristics Reference operating In accordance with DIN EN 29104 conditions • Fluid temperature: +28±2 °C (+82±4 °F) • Ambient temperature range: +22±2 °C (+72±4 °F) • Warm-up period:30 min Installation • Inlet run > 10 × DN •...
Technical data Proline Promag L 400 HART Mechanical load • Protect the transmitter housing against mechanical effects, such as shock or impact; the use of the remote version is sometimes preferable. • Never use the transmitter housing as a ladder or climbing aid.
Proline Promag L 400 HART Technical data Flow limit The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum flow velocity is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow (v) to the physical properties of the fluid: •...
Page 145
Proline Promag L 400 HART Technical data Weight in US units Lap joint flange; fixed flange DN ≥ 350 (14") Nominal diameter ASME, AWWA [mm] [in] Pressure rating [lbs] Class 150 2 ½ Class 150 – Class 150 Class 150 Class 150 –...
Page 146
Technical data Proline Promag L 400 HART Sensor remote version Weight data: • Including sensor connection housing • Excluding the connecting cable • Excluding packaging material Weight in SI units Lap joint flange; fixed flange DN ≥ 350 (14") Nominal...
Page 147
Proline Promag L 400 HART Technical data Lap joint flange, stamped plate Nominal diameter EN (DIN) [mm] [in] Pressure rating [kg] PN 10 2 ½ PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 Weight in US units Lap joint flange;...
Page 148
Technical data Proline Promag L 400 HART Nominal diameter ASME, AWWA [mm] [in] Pressure rating [lbs] 2 000 Class D 6858 – Class D 8273 – Class D 10571 Measuring tube Nominal diameter Pressure rating Measuring tube internal diameter specification...
Page 149
Proline Promag L 400 HART Technical data Nominal diameter Pressure rating Measuring tube internal diameter EN (DIN) ASME AS 2129 Hard rubber Polyurethane PTFE AWWA AS 4087 [mm] [in] [mm] [in] [mm] [in] [mm] [in] PN 10 – – 27.3 27.4...
Page 150
Technical data Proline Promag L 400 HART Nominal diameter Pressure rating Measuring tube internal diameter EN (DIN) ASME AS 2129 Hard rubber Polyurethane PTFE AWWA AS 4087 [mm] [in] [mm] [in] [mm] [in] [mm] [in] – – Class D –...
Page 151
Proline Promag L 400 HART Technical data Compact and remote versions and sensor connection housing Cable entry/cable gland Material Cable gland M20 × 1.5 Plastic Remote version: cable gland M20 × 1.5 • Sensor connection housing: Nickel-plated brass • Option CK "IP68, Type 6P, waterproof"...
Page 152
Technical data Proline Promag L 400 HART Electrodes 1.4435 (304L), Alloy C22 Process connections EN 1092-1 (DIN 2501) • DN ≤ 300 (12"): 1.0038 (S235JRG2), 1.4301 (304), 1.4306 (304L), 1.4307 (304L) • DN ≥ 350 (14"): 1.0038 (S235JRG2), A105 ASME B16.5 •...
Proline Promag L 400 HART Technical data Process connections Flange connections: • EN 1092-1 (DIN 2501) – DN ≤ 300 (12"): lap joint flange (PN 10/16), lap joint flange, stamped plate (PN 10) = form A – DN ≥ 350 (14"): fixed flange (PN 6/10) = flat face •...
EC Directives. These are listed in the corresponding EC Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media Authority (ACMA)".
The application packages can be ordered from Endress+Hauser either directly with the device or subsequently. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Overview of accessories available for order (→ 131) 16.15 Documentation The following document types are available: • On the CD-ROM supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download Standard documentation Communication...
Proline Promag L 400 HART Appendix Appendix 17.1 Overview of the operating menu The following table provides an overview of the entire operating menu structure with menus and parameters. The direct access code to the parameter is given in brackets. The page reference indicates where a description of the parameter can be found in the manual.
Page 158
Appendix Proline Promag L 400 HART Mass flow unit Volume flow unit Density unit Conductivity unit Current span 0/4 mA value 20 mA value Failure mode Failure current PFS output1 to 2 → (→ 74) Pulse output → (→ 74)
Page 159
Proline Promag L 400 HART Appendix Volume unit Density unit Unit totalizer 1 to 3 Minimum frequency value Maximum frequency value Measuring value at minimum frequency Measuring value at maximum frequency Failure mode Failure frequency Invert output signal Switch output →...
Page 160
Appendix Proline Promag L 400 HART Invert output signal Display → (→ 81) Format display Value 1 display 0% bargraph value 1 100% bargraph value 1 Value 2 display Value 3 display 0% bargraph value 3 100% bargraph value 3 Value 4 display Output cond.
Page 161
Proline Promag L 400 HART Appendix Device ID Device type Manufacturer ID Burst command Slot number Timeout Failure mode Failure value Advanced setup → (→ 90) Enter access code (→ 59) System units → (→ 91) Volume flow unit...
Page 162
Appendix Proline Promag L 400 HART Value 2 display Decimal places 2 Value 3 display 0% bargraph value 3 100% bargraph value 3 Decimal places 3 Value 4 display Decimal places 4 Display language Display interval Display damping Header Header text...
Page 163
Proline Promag L 400 HART Appendix Diagnostic list → (→ 123) Diagnostics 1 to 5 → (→ 123) Event logbook Filter options (→ 124) Device information → (→ 125) Device tag Serial number Firmware version Device name...
Page 164
Appendix Proline Promag L 400 HART Measured current 1 Pulse output1 to 2 Output frequency1 to 2 Switch status1 to 2 Data logging → (→ 106) Assign channel 1-4 Logging interval Clear logging data Simulation → (→ 97)
Page 165
Proline Promag L 400 HART Appendix Verification mode Information external device External reference voltage 1 to 2 Start verification Progress Measured values Output values Status Overall result Verification result → Date/time Verification ID Operating time Overall result Sensor Sensor electronic module...
Page 166
Appendix Proline Promag L 400 HART Display language (0104) (→ 70) Format display (0098) Value 1 display (0107) 0% bargraph value 1 (0123) 100% bargraph value 1 (0125) Decimal places 1 (0095) Value 2 display (0108) Decimal places 2 (0117)
Page 167
Proline Promag L 400 HART Appendix (→ 119) Assign behavior of diagnostic no. 443 (0659) Assign behavior of (→ 119) diagnostic no. 531 (0741) (→ 119) Assign behavior of diagnostic no. 832 (0681) Assign behavior of (→ 119) diagnostic no.
Page 168
Appendix Proline Promag L 400 HART Totalizer value 1 to 3 (0911) Totalizer overflow 1 to 3 (0910) Input values → (→ 103) Value status input (1353) Output values → (→ 104) Output current 1 (0361) Measured current output...
Page 169
Proline Promag L 400 HART Appendix Flow damping (6661) Flow override (1839) Conductivity damping (1803) Conductivity measurement (6514) → (→ 86) Low flow cut off Assign process variable (1837) On value low flow cutoff (1805) Off value low flow cutoff...
Page 170
Appendix Proline Promag L 400 HART External value (6504) External density (6630) Fixed density (6623) Sensor adjustment → (→ 92) Installation direction (1809) Integration time (6533) Measuring period (6536) Variable adjust → (→ 92) Volume flow offset (1831)
Page 171
Proline Promag L 400 HART Appendix Output → Current output 1 → (→ 73) Assign current output (0359) Current span (0353) Fixed current (0365) 0/4 mA value (0367) 20 mA value (0372) Measuring mode (0351) Damping (0363) Response time (0378)
Page 172
Appendix Proline Promag L 400 HART Maximum frequency value (0454) Measuring value at minimum frequency (0476) Measuring value at maximum frequency (0475) Measuring mode (0479) Damping output (0477) Response time (0491) Failure mode (0451) Failure frequency (0474) Output frequency 1 to 2...
Page 173
Proline Promag L 400 HART Appendix Configuration → (→ 83) Capture mode (7001) Assign external process variable (7002) Device ID (7007) Device type (7008) Manufacturer ID (7009) Burst command (7006) Slot number (7010) Timeout (7005) Failure mode (7011) Failsafe value (7012) →...
Page 175
Proline Promag L 400 HART Appendix → (→ 108) Diagnostics Actual diagnostics (→ 123) (0691) Previous diagnostics (0690) Operating time from restart (0653) Operating time (0652) Diagnostic list → Diagnostics 1 to 5 (692 to 696) Event logbook →...
Page 176
Appendix Proline Promag L 400 HART Main electronic → temperature Minimum value (6547) Maximum value (6545) Heartbeat* → (→ SD01183D) → Base settings Customer (2754) Location (2755) Performing verification → Year (2846) Month (2845) Day (2842) Hour (2843) AM/PM (2813)
Page 177
Proline Promag L 400 HART Appendix Sensor (12152) Sensor electronics module (12151) I/O module (12145) Monitoring result → Noise (12158) Coil current shot time (12150) Reference electrode potential against PE (12155) Simulation → (→ 97) Assign simulation process variable (1810)