The Boiler Start-Up - Adisa ADI CD 70 Technical Manual Of Installation, Use And Maintenance

Adi cd series
Table of Contents

Advertisement

ADI CD boiler - Technical Manual

18. THE BOILER START-UP

18.1 Before the start-up
The first start-up is a very important operation on which the future effectiveness and reliability of the equipment can
depend. For this reason, it must be carried out by our own Official Technical Assistance Service.
Before the start-up, it is important to check that:
The installation is in accordance with this manual's instructions and with the local regulations.
-
The installation is full of water and vented of air.
-
The static water pressure of the installation (when cold) is between 1 bar minimum and 4 bar maximum.
-
The water circulation pumps operate in the correct direction.
-
The water cut-off valves are open.
-
The gas type and pressure correspond to the ones indicated for that boiler (see the boiler identification plate).
-
The gas valves are open, the air of the gas installation vented and there are no gas leaks.
-
Electrical connections are correct (see electrical supply for every model), the boiler is electrically supplied.
-
The controls are set so as to require heat from the system.
-
Instruments required for the start-up:
A manometer to check the combustion chamber pressure drop, the gas injectors pressure and the inlet gas
-
pressure. We recommend using two digital manometers (or U-shaped manometers with water columns).
A flue electronic analyser to measure CO, CO
-
Ammeter/electrical tester.
-
Ionization electrode, ignition electrode, fuses, screws, nuts.
-
18.2 Gas pressure switch
Model
ADI CD
Adjustment
(mbar)
10
70 – 105
15
120 – 175
Rest of
15
the range
2
Natural Gas pressure switch
Type
Blind cover, open
the cover to adjust
Transparent cover,
fixed to the side of
the gas shut-off
valve
Transparent cover,
connected to a pipe
to facilitate access
, O
and the flues temperature.
2
Image
OFF
ON
10
12.5
+/- 1
+/- 1
15
17.5
+/- 1
+/- 1
15
17.5
+/- 1
+/- 1