Programming Mm453 Setting Page - TECSYSTEM MM453 Instruction Manual

Multichannels monitoring unit
Table of Contents

Advertisement

Press the ▲ ▼ keys to set the Alarm AL1
(or AUX1) threshold.
6
Press the ► key to proceed to step 7.
Press ▲ ▼ keys to set the AL1 (or AUX1) relay
intervention logic when the set threshold is
reached.
Mode 1 (>): intervention for T°>threshold
Mode 2 (<): intervention for T°<threshold
Mode 3 (><): intervention for T°<threshold just ex-
7
ceeded
Mode 4 (><): same logic as mode 3, but with
storage in MEMO page only for the first
alarm occurred among AL1, AL2, AUX1, AUX2
Press ► key to proceed to step 8.
Press the ▲ ▼ keys to set the threshold alarm
AL2 (or AUX2).
8
Press F2 to return to the page PROGRAMMING
MENU
NOTES:
Press the ◄ key to return to the previous step.
Press the F2 key to return to the PROGRAMMING MENU.
Press the F1 key to exit the programming mode if you do not need to set other parameters.
The value of alarm threshold 1 cannot be higher than the threshold value of alarm 2.
PROGRAMMING MM453 PAGE SETTING
Selecting MM453 SETTING it appears the page that allow you to load the MM453 base operating settings.
STEP
FUNCTION DESCRIPTION
The cursor → is placed near the setting on which you
want to operate
Press ▲ ▼ keys to change the selection
1
Press ENTER key to confirm the choice.
NOTE: several optional selections may depend on the
unit model.
By selecting Display Contrast the page to
adjust the display contrast is shown.
2
Press ▲ ▼ keys to modify it.
NOTES:
Press the F2 key to return to the MM453 SETTING
Press the F1 key to exit the programming mode if you do not need to set other parameters.
C H 1 2 O N
A L 0 O N
R e l A L
M o d e 1
C H 1 2 O N
A L 0 O N
R e l A L
M o d e 1
C H 1 2 O N
A L 0 O N
R e l A L
M o d e 1
DISPLAY PAGE
1 → D i s p l a y C o n t r a s t
- - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - -
C O N T R A S T S E T T I N G
MM453 SERIES
P T 1 0 0 S E T
A L 0
C
6 0 ° C
> A L 1
9 0 ° C
> A L 2
1 1 9 ° C
P T 1 0 0 S E T
A L 0
C
6 0 ° C
> A L 1
9 0 ° C
> A L 2
1 1 9 ° C
P T 1 0 0 S E T
A L 0
C
6 0 ° C
> A L 1
9 0 ° C
> A L 2
1 1 9 ° C
M M 4 5 3 S E T T I N G
■ ■ ■ ■ ■ ■
0 1 2 3 4 5 6 7 8 9