11. 6 E+H parameters: Transducer Block "Totalizer 1" or

"Totalizer 2"

The following table shows all the E+H-specific parameters of the Transducer Block "Totalizer 1" or
"Totalizer 2". These can only be changed after entering an enabling code in the "Un-/Locking -
Access Code" parameter.
Transducer Block "Totalizer 1" / "Totalizer 2"
(E+H parameter) / base index 600/700
Parameter
Write access for
operating mode
(MODE_BLK)
!
Note!
The FOUNDATION Fieldbus parameters are described on Page 97
Un-/Locking -
AUTO - OOS
Access Code
Un-/Locking -
Read only
Access Status
Totalizer -
Read only
System Value
11 Operation via FOUNDATION Fieldbus
Description
All data of the measuring system are protected against inadvertent change.
Programming of the manufacturer-specific parameters is disabled and the
settings cannot be changed until a code is entered in this function.
You can enable programming by entering the:
• Code 73 (factory setting)
• Personal code, see "Un-/Locking – Define Private Code" parameter (see
Page 145) Transducer Block "Display"
User input:
Max. 4-digit number (0 to 9999)
!
Note!
• If write protection is enabled, access to manufacturer-specific parameters
is denied even if the right code is entered. Write protection can be
enabled or disabled by means of DIP switches (see Page 36).
• You can disable programming again by entering any number in this
function (other than the Private Code).
• The Endress+Hauser service organization can be of assistance if you
mislay your private code.
• Certain parameters can only be altered if a special Service Code is
entered. This Service Code is known to your Endress+Hauser service
organization. Please contact your Endress+Hauser service point if
anything needs clarification.
Use this function to display the current status of the possibilities for accessing
the manufacturer-specific parameters of the device.
Display:
• LOCKED (parameters cannot be modified)
• ACCESS CUSTOMER (parameters can be modified)
• ACCESS SERVICE (parameters can be modified, access to service level)
The total for the totalizer's measured variable aggregated since measuring
commenced appears on the display.
The value of the totalizer is made available as a process variable to the
downstream Analog Input Function Blocks.
!
Note!
• The unit is displayed in the "Totalizer - System Unit" parameter (see
Page 118).
• The behavior of the totalizers in the event of a fault is determined in the
"Totalizer - Failsafe Mode" parameter (see Page 120).