CS-SA18CKP / CU-SA18CKP5
Outdoor Unit
60-seconds Test Operation Control
Once the compressor is activated, it does not
stop for 60 seconds. It stops immediately with
remote controller ON/OFF button.
Deicing Control
Anti-freezing operation for outdoor unit(during
Heating Mode Operation only)
Temperature of the condenser is tested by TRS.
Overload Protection Control
When the temperature of evaporator
reaches 51 ,outdoor fan stops, and will
restart when the temperature of evaporator
declines to 49 .
When the temperature of evaporator
reaches 65 ,compressor will stop.
C
C
C
4-way Valve Control
If the unit is stopped during Heating
Operation, the 4-way valve will remain in
heating mode operation mode for 5 minutes.
Outdoor Fan Operation Control
Fan motor(4 poles, 2 speeds)
Cool: When the outdoor temperature is more
than 31 ,the speed is at High; When
the outdoor temperature is less than
29 , the speed is at Low.
C
Heat: When the outdoor temperature is less
than 13.5 ,the speed is at High; When
the outdoor temperature is more than
15.5 , the speed is at Low.
C
4
C
C