Haier MVHP036MV2AA Installation Manual page 21

Outdoor unit
Table of Contents

Advertisement

Installation and debugging
3. Outdoor unit PCB dipswitch setting(Pay attention to the identification of the computer board).
In the following table, 1 is ON, 0 is OFF.
BM1 introduction
BM1_1 Indoor searching after startup
BM1_2 Celsius/Fahrenheit area selection
BM1_3 External static pressure
BM1_4 Energy saving or refrigeration effect priority
BM1_5 Indoor simultaneous control
BM1_6 Defrosting condition selection
BM1_7 Defrosting level
BM1_8 Silent operation selection
BM2 introduction
BM2_1 Cold only or heat pump
BM2_2
BM2_3
Outdoor horse power selection
BM2_4
BM2_5 Power source selected
BM2_7
Running mode preference
BM2_8
Note: Either indoor unit unlocked or the locked quantity different with actual connecting number, it cannot run.
4. bridge instruction
CJ1:
Short it before power ON-- PCB check its function (used for factory production).
Short it after power ON-- time short function, 60 seconds become to 1 second.
CJ2: Reserved
0
Begin to search indoor
1
Stop searching indoor and lock the quantity
0
Celsius area
1
Fahrenheit area
0
High
1
Low
0
Energy saving priority
1
Refrigeration effect priority
0
No
1
Yes
0
Not easy to frost area
1
Easy to frost area
0
Ordinary
1
Strengthen
0
Forbidden(without silent operation)
1
Allow (with silent operation)
[1]
Cold only or heat pump
0
Heat pump(default)
1
Cold only
[2]
[3]
[4]
1
0
0
1
0
1
1
1
0
[5]
Power source selected
0
Single-phase
1
Three-phase
[7]
[8]
Running mode preference
0
0
Start first(default)
0
1
Later start first
1
0
Cooling first
1
1
Heating first
19
Outdoor horse power selection
36
48
56