Siemens 6ES7134-4JB00-0AB0 Manual page 27

Distributed i/o 2ai tc st analog electronic module
Table of Contents

Advertisement

Non-isolated measuring encoders
The non-isolated measuring encoders are connected to the local ground potential. You must
connect M
potential differences U
measuring points.
If the permitted value for U
between the measuring points.
The following schematic representation illustrates the connection of non-isolated measuring
encoders to an optically isolated analog input module.
Connection of non-isolated measuring encoders to an optically isolated analog input module:
5
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
to the ground potential. Depending on local conditions or interference,
ANA
(static or dynamic) can occur between the locally distributed
CM
4
Logic
Backplane bus
Ground bus
Equipotential bonding conductor
Non-isolated measuring encoders
is exceeded, there must be equipotential bonding conductors
CM
3
5.1 Connecting measuring sensors
1
2
Connecting
27