Setting Temperature

Use the UP and DOWN temperature buttons to change
the heating and cooling setpoints. To conserve energy
and make sure that the heating and cooling units do
not fi ght each other, the heating and cooling setpoints
typically cannot be set closer than 5 °F. Other "ON-
OFF differentials" may be used. 3, 4 or 6 °F can be
selected via the communications interface.
The range of local temperature adjustment may be
restricted to owner specifi cations.
On some models the temperature buttons may not
function.
If the temperature buttons function and they are used,
the word "OVERRIDE" will appear in the display. The
override period is determined by the communications
interface. When the override period expires, the
e-Stat
will revert back to its program.
e-Stats
Note: Not all
allow button adjustment of
temperature settings during the OCCUPIED period.
During the UNOCCUPIED program period pressing
either up or down buttons will adjust the setpoints to
the settings defi ned for the previously occupied state.
The previously occupied state setpoints will remain
in effect for 2 hours (time frame is adjustable) before
reverting back to the setpoints defi ned in the current
program. If previously occupied state data is
unavailable for the current day, default temperature
settings are used.